Catalogue ELS/SV - Lumentron Electronic Kft.
Catalogue ELS/SV - Lumentron Electronic Kft.
Catalogue ELS/SV - Lumentron Electronic Kft.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
4<br />
The free programmable control<br />
module with two-line liquid crystal<br />
display for plain text information<br />
has three main tasks:<br />
Monitor and control all internal<br />
functions and test-cycles, allow<br />
manual interaction<br />
Display all panel and luminaire<br />
information<br />
(failure and status info)<br />
Safe all information concerning tests,<br />
status of luminaries and panel for<br />
log-book purpose<br />
The display shows:<br />
Battery voltage<br />
Battery charging current<br />
Battery discharge current during test<br />
or emergency operation<br />
Charging failures<br />
- battery voltage to high / low<br />
- interrupted charge circuit<br />
- required duration test time not<br />
achieved<br />
Luminaire failure<br />
LED display the following<br />
mandatory status info:<br />
Operation (mains supply healthy)<br />
Batt.-Operation<br />
Operation<br />
Failure<br />
1 2 3 4 5 6<br />
Battery operation (test or mains<br />
failure)<br />
Failure (luminaire-, system- or mains<br />
Remote Control<br />
failure)<br />
Charging failure<br />
Operation<br />
Batt.-Operation<br />
Failure<br />
Charging failure<br />
The four push-buttons next to the<br />
display allow the programming of the<br />
system, the manual release of tests and<br />
the status- and failure interrogation for<br />
230V / AC<br />
output<br />
the individual CH1 CH2 system. CH3 CH4The<br />
pre-set 50 / 60 tests Hz 1 2 3 4<br />
FS 24V RTG B SL L N L N L N L N PE N L<br />
NLPE NLPE NLPE NLPE<br />
(function-test usually every 7 days,<br />
battery duration test usually every 12<br />
month) are Light free Switch programmable. The<br />
display text Indicator is adapted to the native<br />
language.<br />
Menue<br />
Enter<br />
Change<br />
Test<br />
3,15 AT<br />
<strong>ELS</strong> - <strong>SV</strong><br />
Control module, charger and change-over devices<br />
3,15 AT<br />
3,15 AT<br />
Every INOTEC emergency lighting<br />
system contains components<br />
guaranteeing, together with the<br />
connected luminaries, a maximum<br />
on function and safety.<br />
The constant current charger 3 Amps is<br />
monitored via the control module.<br />
The battery recharging time is < 10 h.<br />
Every one of the 4 change-over devices<br />
supplies up to 15 INOTEC safety- or exit<br />
luminaries. During mains supply 230V,<br />
50/60Hz are present on the output; in<br />
emergency or test mode this supply<br />
comes from the battery pack.<br />
3,15 AT<br />
3,15 AT