� Faulty indoor unit fan motor<br />
� Excessive refrigerant<br />
� Clogged expansion valve or strainer<br />
� Faulty indoor pipe temperature sensor<br />
� Faulty indoor unit PCB<br />
Troubleshooting<br />
77