Indoor Unit Outdoor Unit CS-E24NKES CS-E28NKES CU-E24NKE ...
Indoor Unit Outdoor Unit CS-E24NKES CS-E28NKES CU-E24NKE ...
Indoor Unit Outdoor Unit CS-E24NKES CS-E28NKES CU-E24NKE ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
15.5.24 F95 (Cooling High Pressure Abnormality)<br />
Malfunction Decision Conditions<br />
� During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the<br />
outdoor pipe temperature sensor.<br />
Malfunction Caused<br />
� Air short circuit at indoor unit<br />
� Dust accumulation on the indoor unit heat exchanger<br />
� 2/3 way valve closed<br />
� Faulty outdoor unit fan motor<br />
� Excessive refrigerant<br />
� Clogged expansion valve or strainer<br />
� Faulty outdoor pipe temperature sensor<br />
� Faulty outdoor unit PCB<br />
Troubleshooting<br />
84