. Set PG/PC interface<br />

This step is important fort he following software<br />

� SIMATIC Step© 7 Manager (v5.2 + SP1)<br />

� Windows Control Center (WinCC) (v6.0)<br />

� Windows Control Center flexible 2004 (WinCC flexible) v5.2.0.0<br />

� ProTool/Pro (v6.0 + SP2)<br />

� Microwin<br />

If the software you are using is not in the list above you can skip setting up the<br />

PG/PC interface.<br />

1. Open the system configuration by using the start<br />

menu.<br />

2. Click on „Set PG/PC interface“.<br />

3. A Dialog with a list box named „Interface Parameter<br />

Assignment Used:” appears. This box should offer<br />

some „PC - Adapter” and/or „TCP/IP” (if you<br />

want to use RFC1006) entries. If you cannot<br />

find these entries go ahead with the steps<br />

PC Adapter or TCP/IP otherwise skip these<br />

steps.<br />

PC - Adapter(Auto, MPI, PROFIBUS)<br />

4. Click on „Choose“ to add these entries to the<br />

PG/PC interface configuration.<br />

5. In this dialog you can deinstall every<br />

installed construction set and install the entries in the „Selection“ box. Choose<br />

„PC - Adapter“ from the „Selection“ box on the left side and click on „Install“. The<br />

chosen construction set will be<br />

installed and a question appears<br />

which asks you to use the<br />

„MPI“ access for the PLC used.<br />

Click „Yes“ if you want to use<br />

the „MPI“ communication type.<br />

Otherwise click „No“ (e.g. if you<br />

want to use the<br />

“PROFIBUS“ communication<br />

type).<br />

Page 16 Cable and adapter manual © by PI 2008