General requirements

5.6. Requirements for work equipment

in hazardous areas

To enable work equipment to be used in hazardous

areas (potentially explosive atmospheres, PEA), it

must be approved for use in the respective Ex zone.

European Directive 2014/34/EU (ATEX, 2014)

(ATEX Product Directive, referred to in the following

simply as ATEX), has become established as the basis

for the use of equipment and protective systems

in Ex zones (see Figure 9).

According to this directive, only equipment that is

approved for zone 0 and is correspondingly marked

may be used in zone 0. Only equipment and protective

systems of equipment group II category 1 G according

to Annex 1 of ATEX may be used.

In zone 1 only equipment that is approved for zone

0 or 1 and is correspondingly marked may be used.

Only equipment and protective systems of equipment

group II category 1 G or 2 G according to Annex

1 of ATEX may be used.

In zone 2 only equipment that is approved for zone 0,

1 or 2 and is correspondingly marked may be used.

Only equipment and protective systems of equipment

group II category 1 G, 2 G or 3 G according to

Annex 1 of ATEX may be used.

Details of the zoning must be recorded in an Ex

zone plan (see Figure 10). This must be regularly

checked to ensure that it is up-to-date, and adapted

as necessary.

Figure 10: Example of a Ex-zone plan for a biogas

plant (red = zone 1, orange = zone 2)

➀ Overpressure and underpressure protection

➁ Wall duct for submersible mixer

➂ Outlet of the membrane gas storage tank

➃ Blower of the membrane gas storage tank

➄ Space in between the membranes of the gas storage

Source: Inreetec GmbH