Specific requirements

Organisational protective measures

A piping layout plan (including the position and type

of valves, fittings, connecting pipes and supports)

must be drawn up which shows the material and size

of the pipework, the pipe run and the integration of

the pipework in the biogas plant.

Gate valves, especially those on filling equipment,

and other shut-off devices (inspection openings, but

also pumps) must be secured to prevent unauthorised

opening.

The operator must regularly check all visible pipes

for leaks by visual inspection and must document

the inspection.

9. Requirements for gas-carrying parts of the biogas plant

for hydraulic engineering installations such as digesters,

condensate shafts or other structures.

In gas pipes leading to consumption equipment

such as heating boilers, gas flares and combined

heat and power units, flame arresters must be fitted

and operated as close as possible to the end-use

equipment.

Spigot-and-socket joints that are not in themselves

longitudinally force-locked must be secured against

thrust according to the pressures arising. The pipe

connections must be longitudinally force-locked.

Gas pipes (and labelling)

Technical protective measures

Gas-carrying parts of the biogas plant must be protected

against chemical, weather-related and – in

vulnerable areas – mechanical influences and damage

(e.g. collision impact protection guards in areas

where vehicles move).

Gas-carrying pipes must conform to national requirements,

with proof of proper manufacture, suitability

for biogas and leak-tightness, for example by manufacturer

certification. Requirements arising from

structural analysis (wind, snow load etc.) must be

taken into consideration when selecting pipe materials

and calculating spans. The installation instructions

provided by the manufacturers of the pipes and

wall bushings must be observed when routing pipes

through buildings (e.g. gas and substrate pipes) and

photo: Schmack

Mechanical damage from settlement (for example in

the case of wall bushings) must be prevented through

the use of suitable bushings and appropriate connections.

If the gas is wet, it is important to ensure

the pipes are protected from frost. Condensate discharge

pipes must be designed to be frost-proof and

operational at all times. Pipes connecting to the gas

storage tank inside the gas storage tank’s installation

room are considered part of the gas storage tank.

Two shut-off valves must be installed in the gas line

upstream of each engine unit. The valves must close

automatically when the engine stops. The interspace

must be regularly checked for leaks. If the supply

line to the engine has a constant upstream pressure

(> 5 mbar) even when the engine is stopped, automatic

interspace monitoring is required.

Organisational protective measures

Pipes must be labelled to indicate the medium carried

and the direction of flow. When available, the relevant

national guidelines should be followed in this regard.

42