25.11.2019 Views

Biogas Safety first!

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Specific requirements

ventilation system in its various possible operating

states. The evaluation units must be installed outside

the room being monitored.

The forced ventilation system must be dimensioned

such that a maximum possible gas volume is diluted

to a maximum gas concentration of 20 % LEL in the

installation room.

At an alarm threshold of 20 % LEL (0.9 % v / v CH 4

)

in the room air, the response should be visual and

audible warnings and air intake or extraction at

100 % power.

At for example 40 % LEL (1.8 % v / v CH 4

) in the

room air, the response should be visual and audible

warnings, air intake or extraction at 100 % power

and automatic shut-off of gas supply outside the installation

room.

The gas warning device continues to operate after

the second alarm threshold is exceeded, i.e. it is not

switched off.

If a technical ventilation system is installed it must

be ensured that the exhaust air is extracted from

the ceiling area. The exhaust air must be expelled

directly into the atmosphere.

!

TIP

The minimum free cross-section ‘A’ of the

air inlet/air outlet of CHP unit installation

rooms is obtained from the following equation:

A = 10P+175A = free crosssection (cm 2 )

P = maximum declared electrical output from

the generator, kW el

Examples:

22 kW el

= 395 cm² and 30 kW el

= 475 cm²

Further requirements for CHP unit

installation rooms:

CHP unit installation rooms must be dimensioned

such that the combined heat and power units can be

properly installed, operated and maintained. This is

generally the case if the CHP units are accessible

on three sides. Doors must open in the direction of

escape. If CHP units are operated inside containers,

later replacement should be possible without difficulty.

The air flow parameters prescribed by the CHP

unit manufacturer should be reliably achievable in

the CHP unit installation room.

The CHP unit must be mounted on its foundations

and installed such that the unit’s vibrational load is

below the vibration levels permissible for continuous

operation.

Floor drains must have oil traps. Alternatively, a collection

tank to catch the entire volume of oil must be

positioned beneath the engine.

It must be possible to shut down the CHP unit at

any time by means of an illuminated switch outside

the installation room. The switch must have

a clearly visible, durable label ‘Emergency Stop

Switch – CHP Unit’ and must be accessible. The

same requirements also apply to electrically operated

shut-off valves.

Two shut-off valves must be installed in the gas line

upstream of each engine unit. The valves must close

automatically when the engine stops. The interspace

must be regularly checked for leaks. If the supply

line to the engine has a constant upstream pressure

> 5 mbar (5 hPa) even when the engine is stopped,

automatic interspace monitoring is required.

Doors must open outwards and must be lockable.

Organisational protective measures

The gas warning device must be maintained in accordance

with the manufacturer’s instructions. Gas

warning systems must be tested regularly, at least

once a year. Operating instructions must be drawn

up for cases where the alarm is triggered by the gas

warning device or a fault in the gas warning device.

Classification of Ex zones

Technically leak-tight gas-carrying plant parts combined

with adequate organisational measures, periodic

inspection for leaks. Monitoring of the installation

room for potentially explosive atmospheres: e.g.

at 20 % of LEL triggering of alarm and maximisation

of fan output (at least five air changes per hour), at

40 % of LEL automatic shut-off of gas supply.

No zoning necessary

For further information

about installation rooms, refer to

DIN ISO 10816-6.

53

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!