Specific requirements

emergency power exercise. The emergency power

unit must be properly earthed in order to prevent the

tripping of residual-current-operated circuit breakers.

The labelling of the switchgear cabinet must be

easily comprehensible.

If the emergency power unit is potentially used for

more than one business/type of business:

ensure that in emergency operation each connected

user is able to draw at least the minimum

amount of energy from the emergency power

supply defined in advance;

make technical provisions to ensure that in

emergency operation each connected user

is able to draw only the maximum amount of

energy from the emergency power supply defined

in advance.

18. Requirements for lightning protection

The matter of lightning protection at biogas plants

must be managed in accordance with national regulations

and the regional risk of lightning strikes.

There is a basic distinction between external and

internal lightning protection. Internal lightning protection

serves to prevent surge damage within the

installation. External lightning protection by means

of lightning rods serves to divert lightning strikes

that would hit the protected installation directly.

Technical protective measures

Biogas plants should have at least internal lightning

protection. A surge arrester (internal lightning protection)

and consistent equipotential bonding are

therefore required for the electrical installation and

the facilities for electronic control, data processing

and telecommunications. Experience to date suggests

that external lightning protection (intercepting

devices, arrester equipment, earthing system etc.) is

not generally necessary.

Organisational protective measures

The matter of lightning protection should be taken

into consideration in the hazard assessment carried

out for the construction and operation of the biogas

plant.

Further information concerning

lightning protection can be found

within the norm DIN EN 62305.

19. Requirements for rooms with substrate-carrying and / or

gas-carrying plant parts

Rooms with substrate-carrying and/or gas-carrying

plant parts include the CHP unit installation room,

pump room, etc.

Technical protective measures

General requirements

As a general rule, maintenance and control stations

and the controls of valves, agitation, pumping and

flushing equipment should always be situated above

ground level. If this is not possible, adequate technical

ventilation must be provided with at least five air

changes per hour.

Requirements for CHP unit installation rooms

If it is not possible to ensure that all gas-carrying

plant parts in CHP unit installation rooms are permanently

technically leak-tight, sources of ignition

must be avoided and if applicable explosion protection

zones must be designated. Explosion protection

zones in installation rooms can be restricted or avoided

by taking additional measures, such as a forced

ventilation system with monitoring of the air flow or a

gas warning device coupled with ventilation.

Depending on the nature of the gas, the detecting element

of the gas warning device should be mounted

above or in the vicinity of possible sources of released

gas, taking into account the effects of the