3.3.3 Power supply fusing

Note: A one-amp fuse should be connected in-line with the battery positive terminal to the controller and

modules. These items should never be connected directly to the starting battery.

Fuse value and type depends on number of connected devices and wire length.

Recommended fuse (not fast) type - T1A. Not fast due to internal capacitors charging during power up.

3.3.4 Binary output protections

Note: Do not connect binary outputs directly to DC relays without protection diodes, even if they are not

connected directly to controller outputs.

3.3.5 Grounding

To ensure proper function:

Use as short as possible cable to the grounding point on the switchboard

Use cable min. 2.5mm 2

Note: The “-“ terminal of the battery has to be properly grounded.