4.8 Engine operation states
4.8.1 Engine state machine
Init
Not ready
Prestart
Cranking
Pause
Starting
Running
Stop
Shutdown
Ready
Cooling
EmergMan
AFterCool
Auto test during controller power on
Engine is not ready to start
Prestart sequence in process, Prestart output is closed
Engine is cranking
Pause between start attempts
Starting speed is reached and theIdle time (page 77) is running
Engine is running at nominal speed
Stop
Shut-down alarm activated
Engine is ready to run
Engine is cooling before stop
Emergency Manual engine operation
Engine after cooling - Cooling Pump output is closed
4.8.2 History file
Controller stores a record of each important event into the history file. The history file seats 117 records. When
the history file is full, the oldest records are removed.
Note: To force history download in LiteEdit (direct, modem or Internet) open History window and select History
| Read history command.
ID-Lite FPC 1.6.0 Global Guide 46