4.7.4 List of possible alarms
Information
on binary
Events
specification
Protection
type
output
available
(see List of
Description
LBO on
page 127)
Wrn Oil Press WRN YES Oil pressure is smaller than Wrn Oil press setpoint.
Sd Oil Press SD NO Oil pressure is smaller than Sd Oil press setpoint.
Wrn Engine
Water temperature is greater than Wrn Water temp
WRN YES
Temp
setpoint.
Sd Engine Temp SD NO
Water temperature is greater than Sd Water temp
setpoint.
Wrn Fuel Level WRN YES Fuel level is smaller than Wrn Fuel Level setpoint.
Sd Fuel Level SD NO Fuel level is smaller than Sd Fuel Level setpoint.
Wrn AnInAIO WRN YES Warning alarm configurable on the input of IL-NT-AIO.
Sd AnInAIO SD YES Shutdown alarm configurable on the input of IL-NT-AIO.
Binary input Configurable YES
ConfigurableWarning/Shutdown alarms on the inputs of
controller.
SuppBatt V WRN YES
Power Supply voltage is out of limits given by Batt A
Over V and Batt A Under V Batt B Over V and Batt B
Under V setpoints.
Battery A WRN YES
Battery A voltage is out of limits given by Batt A over V
and Batt A under V setpoints.
Battery B WRN YES
Battery B voltage is out of limits given by Batt B over V
and Batt B under V setpoints.
BatteryFlat SD YES
If the controller switches off during starting sequence
due to bad battery condition it doesn’t try to start again
and activates this protection. The controller displays the
message after its restart.
But when the Sprinkler binary input is active it
overrides all SD alarms and the controller starts
the engine automatically.
Start failed SD YES Engine start failed.
ParamFail NONE NO
Wrong checksum of parameters. Happens typically
after downloading new firmware or changing of the
parameter. The controller stays in INIT mode. Check all
parameters, write at least one new parameter.
Overspeed SD YES
The protection comes active if the speed is greater than
Overspeed setpoint.
Underspeed SD YES During starting of the engine when the RPM reached the
ID-Lite FPC 1.6.0 Global Guide 44