3.4.1 Configuration
Each analog input can be configured by LiteEdit (3.0 or higher) software following way.
Analog input
item
LiteEdit
Possibility
Type
Type
Not used
Alarm
Analog input isn’t used
Analog input
name
Name
Up to 14 ASCII characters
Analog Analog measuring in specified range
Binary: open/close - threshold 750 Ω for AIN1-AIN3 or
Binary
7.5V for AIN6-AIN9.
Config of input Config
Tri-state: open/close - threshold 750 Ω, Failure <10 Ω or >
Tri-state 2400 Ω
Available for AIN1 –AIN3 only
Physical
dimension
Dim bar,%,°C,… Up to 3 ASCII characters (Valid only for analog inputs)
Polarity
Contact
type
Protection
direction
Protection
Sensor
characteristic
Sensor
NC Valid only for binary and three-state inputs
NO Valid only for binary and three-state inputs
Over Overstep. Sensor fail does not activate protection
Over+Fls Overstep and Sensor fail activates protection
Under Under step. Sensor fail does not activate protection
Under+Fls Under step and Sensor fail activates protection
Curve A User curve A
Curve B User curve B
Curve C User curve C
Decimal points Dec 0, 1, 2 Number of decimal points (Valid only for analog inputs)
User Curves A, B, C are adjustable in LiteEdit (3.0 or higher) – use “Points” button..
Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and delay adjust
in Protection or Engine protection group.
Note: Current sensor can be connected to AI1, AI2, and AI3 resistive input when external resistor 120 ohms is
connected between Aix and AI-COM. In such a case use following sensor characteristics.
ID-Lite FPC 1.6.0 Global Guide 20