3.4.1 Configuration

Each analog input can be configured by LiteEdit (3.0 or higher) software following way.

Analog input

item

LiteEdit

Possibility

Type

Type

Not used

Alarm

Analog input isn’t used

Analog input

name

Name

Up to 14 ASCII characters

Analog Analog measuring in specified range

Binary: open/close - threshold 750 Ω for AIN1-AIN3 or

Binary

7.5V for AIN6-AIN9.

Config of input Config

Tri-state: open/close - threshold 750 Ω, Failure <10 Ω or >

Tri-state 2400 Ω

Available for AIN1 –AIN3 only

Physical

dimension

Dim bar,%,°C,… Up to 3 ASCII characters (Valid only for analog inputs)

Polarity

Contact

type

Protection

direction

Protection

Sensor

characteristic

Sensor

NC Valid only for binary and three-state inputs

NO Valid only for binary and three-state inputs

Over Overstep. Sensor fail does not activate protection

Over+Fls Overstep and Sensor fail activates protection

Under Under step. Sensor fail does not activate protection

Under+Fls Under step and Sensor fail activates protection

Curve A User curve A

Curve B User curve B

Curve C User curve C

Decimal points Dec 0, 1, 2 Number of decimal points (Valid only for analog inputs)

User Curves A, B, C are adjustable in LiteEdit (3.0 or higher) – use “Points” button..

Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and delay adjust

in Protection or Engine protection group.

Note: Current sensor can be connected to AI1, AI2, and AI3 resistive input when external resistor 120 ohms is

connected between Aix and AI-COM. In such a case use following sensor characteristics.

ID-Lite FPC 1.6.0 Global Guide 20

Hooray! Your file is uploaded and ready to be published.