<strong>TMS</strong>, GB<br />

Data and features<br />

Function<br />

System <strong>TMS</strong> Basic <strong>TMS</strong> Universal<br />

Opening of door in emergency via emergency pushbutton 3 3<br />

Short-time unlocking, adjustable (3–120 sec) 3 32 3 32<br />

Long-time unlocking 3–60 min. 3 32 3 32<br />

Long-time unlocking with audible acknowledge signal 3 3<br />

Permanent unlocking with audible acknowledge signal 3 3<br />

“Door open” monitoring (1–180 sec) 3 32 3 32<br />

Pre-alarm 3 32 3 32<br />

Main alarm 3 3<br />

Premature re-locking after door closure 32 2<br />

Lever handle pre-alarm 31 3 32<br />

Differentiated visual and audible status signals 3 3<br />

Bi-directional escape door terminal inside/door terminal outside3 31 1<br />

Operation with panel module (TE 20) without local door terminal – 1<br />

Automatic re-activation after power failure 3 3<br />

Automatic locking of the emergency escape lock 3 3<br />

Automatic re-activation by emergency escape lock 3 32 3 32<br />

Mechanical sequential control of the emergency escape lock 3 3<br />

Electrical sequential control of the emergency escape lock<br />

Emergency unlocking by fire alarm system, building control<br />

– 1<br />

system, smoke detector, sprinkler system, etc. 3 3<br />

Passage from inside to outside via door terminal 3 3<br />

Passage from outside to inside via key switch 31 32 1 32<br />

Passage from inside to outside or outside to inside via lock 32 3<br />

Anti-tamper monitoring, TL door terminal 3 3<br />

Anti-tamper monitoring, TV electrical door locking element 3 3<br />

Integrated differential anti-tamper circuit/bus monitoring function 3 3<br />

Alarm duration limit 3 32 3 32<br />

Pre-alarm/Silent alarm 31 3 32<br />

Connection to 230V AC 3 3<br />

Access control 31 1<br />

Actuation control logic for automatic door operators 31 3<br />

Signal to intruder alarm/Intruder alarm disable input 31 2<br />

Connection of external alarm devices 31 3<br />

Remote monitoring, remote control 31 1<br />

Remote unlocking of the emergency escape lock 31 1<br />

3 = Standard 2 = Selectable/programmable 1 = Option – = Not available<br />