PSM – Power System Module<br />
Measurement bars for direct<br />
connection without gateway to<br />
the Rittal CMC III system. With a<br />
PSM mounting kit, the measurement<br />
bar may be vertically<br />
mounted in a 2000 mm high<br />
Rittal TS 8 or in the TS IT rack.<br />
Display and monitoring of all<br />
major output parameters is supported,<br />
separated by phase and<br />
infeed. An integral display provides<br />
a local on-site display in<br />
the rack.<br />
Remote administration and network<br />
connectivity are created via<br />
the CMC III system.<br />
PSM measurement bar for CMC III<br />
Benefits:<br />
� Modular extendible system<br />
� For 16 A and 32 A phase<br />
current<br />
� Various PSM connection<br />
modules (pin patterns)<br />
� PSM modules may be<br />
connected with the system<br />
operational<br />
� VDE-tested, shock-hazardprotected<br />
system<br />
� Easy to assemble<br />
� CAN bus for connection to<br />
CMC III system<br />
� Extensive management and<br />
monitoring functions<br />
(via CMC III)<br />
� High-MTBF and measurement<br />
accuracy of 1%<br />
� Energy-efficient electric design<br />
– minimal intrinsic consumption<br />
� High-quality aluminium housing,<br />
for flexible mounting<br />
Measurement functions:<br />
− Voltage (V), current (A),<br />
frequency (Hz)<br />
− Active power (kW),<br />
active energy (kWh),<br />
apparent power (VA),<br />
apparent energy (kVAh)<br />
− Power factor (cos phi)<br />
− Zero conductor measurement/<br />
load imbalance detection<br />
− Measurement per phase or<br />
infeed<br />
− Measurement accuracy 1%<br />
(kWh) to IEC 50 430-1<br />
Material:<br />
Extruded aluminium section,<br />
anodised<br />
Protection category:<br />
IP 20 to IEC 60 529<br />
Standards:<br />
− EN 60 950<br />
− EN 61 000-6-1<br />
− EN 61 000-6-2<br />
− EN 55 022<br />
Safety directive:<br />
2006/95/EC<br />
EMC directive:<br />
2004/108/EC<br />
Model No. DK 7859.050 7859.053<br />
Version/rated current (per phase) 16 A 32 A<br />
No. of infeeds (3-phase, 16 A/single-phase, 32 A) 2 1<br />
Connection cable, plug-in, various versions � –<br />
Connection cable, static, 3 m, with CEE connector, 32 A, single-phase (IEC 60 309) – �<br />
Electromagnetic safety switch (32 A, type C) – �<br />
Input voltage 230 V/400 V (50/60 Hz) � �<br />
Power supply via CMC III system (24 V DC) � �<br />
CAN bus for direct connection to CMC III system (RJ 45, 2 x socket) � �<br />
Maximum no. of systems that may be connected to one CMC-PU III<br />
Ambient conditions<br />
8 8<br />
Operating temperature/storage temperature 0 to 45 °C/–25 to +70 °C<br />
Ambient humidity (non-condensing)<br />
Accessories<br />
10 to 95%<br />
PSM connection cable, 3-phase, with CEE connectors (IEC 60 309), length 3 m<br />
(2 x required when using both infeeds)<br />
7856.025 Fixed installation<br />
PSM mounting kit for mounting on the enclosure frame 7856.011 7856.011<br />
PSM module 4 x earthing-pin, black 7856.100 7856.100<br />
PSM module 4 x earthing-pin, red 7856.240 7856.240<br />
PSM module 6 x C13 7856.080 7856.080<br />
PSM module 4 x C19 7856.230 7856.230<br />
PSM module 3 x UK connectors (BS 1363) 7856.160 7856.160<br />
Other PSM modules<br />
� Included with the supply.<br />
see Cat. 33, page 385<br />
96 Rittal <strong>Innovations</strong> <strong>2012</strong>