PSM – Power System Module<br />

Measurement bars for direct<br />

connection without gateway to<br />

the Rittal CMC III system. With a<br />

PSM mounting kit, the measurement<br />

bar may be vertically<br />

mounted in a 2000 mm high<br />

Rittal TS 8 or in the TS IT rack.<br />

Display and monitoring of all<br />

major output parameters is supported,<br />

separated by phase and<br />

infeed. An integral display provides<br />

a local on-site display in<br />

the rack.<br />

Remote administration and network<br />

connectivity are created via<br />

the CMC III system.<br />

PSM measurement bar for CMC III<br />

Benefits:<br />

� Modular extendible system<br />

� For 16 A and 32 A phase<br />

current<br />

� Various PSM connection<br />

modules (pin patterns)<br />

� PSM modules may be<br />

connected with the system<br />

operational<br />

� VDE-tested, shock-hazardprotected<br />

system<br />

� Easy to assemble<br />

� CAN bus for connection to<br />

CMC III system<br />

� Extensive management and<br />

monitoring functions<br />

(via CMC III)<br />

� High-MTBF and measurement<br />

accuracy of 1%<br />

� Energy-efficient electric design<br />

– minimal intrinsic consumption<br />

� High-quality aluminium housing,<br />

for flexible mounting<br />

Measurement functions:<br />

− Voltage (V), current (A),<br />

frequency (Hz)<br />

− Active power (kW),<br />

active energy (kWh),<br />

apparent power (VA),<br />

apparent energy (kVAh)<br />

− Power factor (cos phi)<br />

− Zero conductor measurement/<br />

load imbalance detection<br />

− Measurement per phase or<br />

infeed<br />

− Measurement accuracy 1%<br />

(kWh) to IEC 50 430-1<br />

Material:<br />

Extruded aluminium section,<br />

anodised<br />

Protection category:<br />

IP 20 to IEC 60 529<br />

Standards:<br />

− EN 60 950<br />

− EN 61 000-6-1<br />

− EN 61 000-6-2<br />

− EN 55 022<br />

Safety directive:<br />

2006/95/EC<br />

EMC directive:<br />

2004/108/EC<br />

Model No. DK 7859.050 7859.053<br />

Version/rated current (per phase) 16 A 32 A<br />

No. of infeeds (3-phase, 16 A/single-phase, 32 A) 2 1<br />

Connection cable, plug-in, various versions � –<br />

Connection cable, static, 3 m, with CEE connector, 32 A, single-phase (IEC 60 309) – �<br />

Electromagnetic safety switch (32 A, type C) – �<br />

Input voltage 230 V/400 V (50/60 Hz) � �<br />

Power supply via CMC III system (24 V DC) � �<br />

CAN bus for direct connection to CMC III system (RJ 45, 2 x socket) � �<br />

Maximum no. of systems that may be connected to one CMC-PU III<br />

Ambient conditions<br />

8 8<br />

Operating temperature/storage temperature 0 to 45 °C/–25 to +70 °C<br />

Ambient humidity (non-condensing)<br />

Accessories<br />

10 to 95%<br />

PSM connection cable, 3-phase, with CEE connectors (IEC 60 309), length 3 m<br />

(2 x required when using both infeeds)<br />

7856.025 Fixed installation<br />

PSM mounting kit for mounting on the enclosure frame 7856.011 7856.011<br />

PSM module 4 x earthing-pin, black 7856.100 7856.100<br />

PSM module 4 x earthing-pin, red 7856.240 7856.240<br />

PSM module 6 x C13 7856.080 7856.080<br />

PSM module 4 x C19 7856.230 7856.230<br />

PSM module 3 x UK connectors (BS 1363) 7856.160 7856.160<br />

Other PSM modules<br />

� Included with the supply.<br />

see Cat. 33, page 385<br />