Air-ducting system<br />

for TopTherm roof-mounted cooling units<br />

With the air duct system, it is possible to route the cold air<br />

directly to specific areas of the enclosure. This effectively<br />

eliminates the risk of “short circuits” in the air circulation due<br />

to self-ventilated components.<br />

Note:<br />

● Never direct the cold air flow straight at active components.<br />

● Route the air duct system directly downwards with no<br />

bends.<br />

● Cold air must be able to escape unobstructed at the end of<br />

the duct.<br />

● Additional deflections will reduce the useful cooling output.<br />

● When using the ducting system, the performance of the<br />

cooling unit may be reduced, depending on the respective<br />

application.<br />

● The air duct system should not be extended.<br />

CAUTION Risk of icing!<br />

Stopper<br />

for TopTherm roof-mounted cooling units<br />

For sealing any cold air outlets that are not required.<br />

Note:<br />

At least one outlet opening must always remain open!<br />

Please note that if two or three openings are closed, the cooling<br />

output may be reduced by 20 % and 30 % respectively!<br />

<strong>SK</strong> 3286.880 for units<br />

<strong>SK</strong> 3383.xxx<br />

<strong>SK</strong> 3384.xxx<br />

<strong>SK</strong> 3385.xxx<br />

<strong>SK</strong> 3286.780 for units<br />

<strong>SK</strong> 3382.xxx<br />

<strong>SK</strong> 3359.xxx<br />

<strong>SK</strong> 3286.980 for units<br />

<strong>SK</strong> 3386.xxx<br />

<strong>SK</strong> 3387.xxx<br />

<strong>Rittal</strong> <strong>System</strong> <strong>Climate</strong> <strong>Control</strong><br />

<strong>SK</strong> 3273.xxx<br />

Accessories:<br />

1 Air duct system for roof-mounted units,<br />

see Cat. 31, page 658.<br />

max. 3x<br />

max. 2x<br />

1<br />

Cooling units<br />

Air routing<br />

37<br />