Assembly and commissioning<br />

In the case of air-cooled recooling systems, the following minimum<br />

distances from the wall and ceiling should be observed:<br />

<strong>Rittal</strong> <strong>System</strong> <strong>Climate</strong> <strong>Control</strong><br />

1<br />

1 Wall: At least 1x condenser height<br />

2 Ceiling: At least 3x the condenser height<br />

2<br />

Recooling<br />

system<br />

Distance from equipment<br />

Site the recooling system<br />

close to the equipment in<br />

order to avoid long distances,<br />

which could lead to<br />

performance losses. When<br />

selecting the installation site,<br />

care should be taken to<br />

ensure easy access at all<br />

times; this will make maintenance<br />

of the system easier.<br />

Cooling media<br />

Apart from the recooling systems<br />

for oil and emulsion, all<br />

other recooling systems are<br />

only suitable for the cooling<br />

of water or a water/glycol<br />

mixture. When filling the systems<br />

for the first time, water<br />

from the existing supply line<br />

is generally suitable,<br />

although care should be<br />

taken to ensure a consistent<br />

water quality.<br />

However, as satisfactory<br />

results are only rarely<br />

achieved without water treatment,<br />

additives should<br />

always be added to the cooling<br />

water, irrespective of the<br />

installation site. As well as<br />

You should also ensure adequate<br />

ventilation of the room<br />

where the recooling system<br />

is sited. If there is inadequate<br />

ventilation, the temperature<br />

of the room will<br />

increase as a result of waste<br />

heat, leading to impaired<br />

performance of the recooling<br />

system.<br />

protecting against frost,<br />

these also serve to impair<br />

bacterial growth and achieve<br />

optimum corrosion protection.<br />

Pre-mixed additive is available<br />

from <strong>Rittal</strong> in the mix<br />

ratios<br />

● 1 : 2 for outdoor siting,<br />

● 1 : 4 for standard applications<br />

in 10 l and 25 l containers.<br />

See Catalogue 31,<br />

page 668.<br />

Recooling systems<br />

Notes/benefits<br />

When siting the recooling system, the following points<br />

should be observed:<br />

● Connection of an inlet and outlet duct shall require the<br />

manufacturer's prior consent.<br />

− Performance loss (air-cooled recooling system)<br />

● Never site the recooling system in the vicinity of a heater.<br />

− Performance loss<br />

● The recooling system may only be sited on flat, solid surfaces.<br />

The maximum permissible deviation from the vertical<br />

is 2°.<br />

● Connect the equipment to the recooling system using insulated<br />

pipe or hose connections.<br />

● If the equipment is positioned higher than the recooling<br />

system, install a non-return valve upstream in the inlet and<br />

a magnetic valve in the return.<br />

− To avoid overflowing the tank.<br />

● With recooling systems that are intended for covered outdoor<br />

siting, the minimum external temperature is given in<br />

the technical specifications.<br />

● In the case of recooling systems (for water) at temperatures<br />

below zero, a water/glycol mixture should be added<br />

in the prescribed ratio.<br />

● If it is possible to shut off the equipment cycle, a bypass<br />

must be provided in order to protect the pump.<br />

● Under no circumstances must the circulation pump be<br />

allowed to run dry.<br />

− Damage to the pump<br />

Benefits<br />

in brief !<br />

● Individual<br />

project handling<br />

● Project planning/<br />

commissioning<br />

from a single partner<br />

● Comprehensive pipeline<br />

calculation<br />

● Global service network<br />

49<br />