Generally speaking, recooling systems are divided into open<br />

and closed systems.<br />

In the pressure-sealed configuration, the water circuit is<br />

equipped with a pressure relief valve and automatic exhaust.<br />

In this way, the cooling medium volume can be routed<br />

directly to the consumer with the integral pump, and no additional<br />

tank reservoir is needed.<br />

Recooling systems designed as an open system have a tank<br />

made of PP plastic or stainless steel 1.4301 built into the<br />

recooling system.<br />

If a recooling system is required to serve several pieces of<br />

equipment having different requirements in terms of inlet temperature<br />

and flow rate of the cooling medium, e.g. combined<br />

enclosure and process cooling, multi-circuit systems are<br />

used. In such cases, the different circuits may be tailored to<br />

the respective equipment.<br />

If there is already a central cooling water supply available at<br />

the installation site, e.g. in the case of plant water in the automotive<br />

industry, recooling systems may optionally be fitted<br />

with a water-cooled condenser. One of the major benefits of<br />

this solution lies in the fact that the factory temperature is not<br />

additionally raised by waste process heat.<br />

Application diversity of centralised cooling technology<br />

Mini-recooling systems<br />

● Cooling output from 960 to<br />

4,500 W<br />

● Space-saving, compact<br />

design<br />

● Attractive design<br />

● Wall-mounted units: Integration<br />

into the machine<br />

and enclosure housing<br />

without using additional<br />

floor space<br />

Recooling systems in a<br />

floor-standing enclosure<br />

for water and oil<br />

● Cooling output from 2,100<br />

to 26,100 W<br />

● Stand-alone enclosure<br />

● Minimal base area<br />

● The functionally equipped<br />

design facilitates the cooling<br />

of oil and water.<br />

Immersible recooling<br />

systems<br />

● Wherever it is necessary<br />

to cool dirt-contaminated<br />

media (metal swarf<br />

or aggressive sludge)<br />

● High-end flat condenser of<br />

stainless steel<br />

● Sealed cooling circuit<br />

<strong>Rittal</strong> <strong>System</strong> <strong>Climate</strong> <strong>Control</strong><br />

Recooling systems integrated<br />

into the TS 8 Top<br />

enclosure system<br />

● Cooling output from 6,000<br />

to 25,000 W<br />

● Compact design<br />

● Option of integration into<br />

existing TS 8 enclosure<br />

combinations<br />

Recooling systems in an<br />

industrial enclosure<br />

● Cooling output from 32 to<br />

172 kW<br />

● High cooling output with<br />

optimised space requirements<br />

● Removable enclosure<br />

panels offer easier accessibility<br />

in case of servicing<br />

Data centre<br />

with recooling systems<br />

● Recooling systems ensure<br />

central cooling and supply<br />

of the cooling<br />

medium for liquid cooling<br />

systems<br />

● Spatial separation<br />

between refrigeration and<br />

cooling for temperatureneutral<br />

expansion of the<br />

data centre<br />

Recooling systems<br />

Selection criteria<br />

45<br />

5.2