Intelligent control<br />

The two controller variants for operational reliability offer a<br />

comprehensive range of functions. Essential control electronics<br />

are well protected and cooled in the inner circuit.<br />

Both variants have the following properties:<br />

● Three voltage options: 115 V, 230 V, 400/460 V 3 ˜<br />

● Integral start-up delay and door limit switch function<br />

● Icing protection function<br />

● Monitoring of all motors<br />

● Phase monitoring for three-phase units<br />

Basic controller:<br />

● Visualisation of the operating status via LED display:<br />

− Voltage applied, functions OK<br />

− Door open<br />

− Overtemperature<br />

− High-pressure monitor has switched<br />

● Switching hysteresis: 5 K<br />

● Floating fault signal contact in case of overtemperature<br />

● Setpoint adjustable from outside via potentiometer (setting<br />

range 20 <strong>–</strong> 55 °C)<br />

<strong>Rittal</strong> <strong>System</strong> <strong>Climate</strong> <strong>Control</strong><br />

Cooling units<br />

Electrical connection and control<br />

Comfort controller:<br />

● Master / slave function for up to 10 units, i.e. the unit which<br />

reaches the setpoint first reports this to the “master”, which<br />

switches all the other “slaves” on and off. The unit in which<br />

the door limit switch function is activated reports this to the<br />

“master”, which deactivates all the “slaves”.<br />

● Switching hysteresis: 2 <strong>–</strong> 10 K; preset to 5 K<br />

● <strong>System</strong> alarm, individually configurable for 2 floating fault<br />

signal contacts<br />

● Visualisation of the current enclosure internal temperature<br />

and all system messages on the display<br />

● Storage of all system statuses in the log file<br />

● Optional extension card (<strong>SK</strong> 3124.200) with RS 232,<br />

RS 485, RS 422 and PLC interface for integration into<br />

superordinate remote control systems, e.g. with CMC, is<br />

also possible<br />