<strong>Refrigeration</strong> Division<br />

Grasso<br />

Bare compressor or loose components:<br />

Determine the dead weight of the particular<br />

component (see "Engineering<br />

Data"), prior to moving a bare compressor<br />

or loose component. Use the hoisting<br />

eyes only to lift so, DO NOT sling<br />

from other compressor parts (see figure<br />

A1.1A).<br />

Fig. A1.1A Hoisting angle bare shaft compressor<br />

Moving by fork-lift truck<br />

The bare compressor or package can be<br />

transported with a fork-lift truck with the forks<br />

spread as much as possible between the skids. To<br />

simplify moving, the 2 wooden transport beams<br />

must still be mounted underneath the base frame<br />

<strong>and</strong> stored in this way, untill the package is<br />

positioned above its approximate location.<br />

A: INSTALLATION AND PREPARATION FOR USE<br />

A1.1.2 Storage<br />

The compressor (package) is filled with dry<br />

nitrogen. Keep the system closed until the<br />

package is<br />

installed. If the compressor (package) is stored, it<br />

should be kept at all times in a dry location to<br />

prevent corrosion damage. If the compressor<br />

(package) is to be stored for a prolonged period<br />

of time, it should be checked weekly to ensure<br />

that the holding charge of dry nitrogen remains<br />

above atmospheric pressure.<br />

A1.2 Required free space<br />

For easy operating, servicing <strong>and</strong> maintenance<br />

access, the compressor (package) should be at<br />

least installed with sufficient free space around it.<br />

A1.3 Foundation requirements<br />

This paragraph covers measures to be taken for a<br />

compressor (package) on a concrete floor.<br />

Two foundation arrangements are described:<br />

• Compressor package with steel base frame<br />

mounted on a concrete block.<br />

• Bare compressor direct mounted on a concrete<br />

block via grouted machined anchors (see<br />

"Engineering Data"). The mounting surfaces of<br />

these machined anchors must be level without<br />

any deviation <strong>and</strong> projecting at least 10 mm<br />

above the concrete base.<br />

COMPRESSOR AND COMPRESSOR<br />

PACKAGE TO BE MOUNTED ON A<br />

CONCRETE BLOCK<br />

On request, Grasso can calculate the<br />

exact dimensions of the concrete block,<br />

based on the compressor size <strong>and</strong><br />

operating conditions.<br />

A1.2 <strong>Installation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> <strong>RC</strong>(U)6 v001.99.01.en