<strong>Refrigeration</strong> Division<br />

Grasso<br />

provided instead with only a simple vertical<br />

partition to keep the common suction <strong>and</strong><br />

discharge chambers in the compressor housing<br />

apart from each other.<br />

Consequently, when the discharge pressure is<br />

higher than the suction pressure, only partially<br />

unloaded starting is possible.<br />

Therefore, it is recommended to always check the<br />

electric drive motor in this respect, depending on<br />

compressor design speed <strong>and</strong> starting conditions,<br />

the procedure of which is set out in paragraph 4.7.<br />

3.5 ALTERNATIVES TO CAPACITY CONTROL<br />

The four-cylinder compressor types <strong>RC</strong>46 can also be<br />

delivered with an alternative capacity control,<br />

including three part-load steps (25, 50 <strong>and</strong> 75%)<br />

instead of only one (50%) in the st<strong>and</strong>ard version.<br />

For the switch sequence of cylinders <strong>and</strong> solenoid<br />

valves of this alternative capacity control, refer to<br />

figure 3.3 <strong>and</strong> figure 3.7 for compressor types<br />

<strong>RC</strong>46 <strong>and</strong> <strong>RC</strong>46W respectively.<br />

These additional steps are obtained by replacing<br />

the non-controllable cylinder head cover of<br />

cylinders nr. 1 <strong>and</strong> 3 (<strong>RC</strong>46 in fig. 3.3) or cylinders<br />

nr. 2 <strong>and</strong> 4 (<strong>RC</strong>46W in fig. 3.7) by a partly<br />

controllable one of special design, which means<br />

that it has a partition in the middle of the space<br />

direct above the discharge valves to separate the<br />

two adjacent cylinders entirely from each other,<br />

thereby causing the built-in control piston <strong>and</strong><br />

slide valve to be effective for cylinder nr. 1 (<strong>RC</strong>46)<br />

or cylinder nr. 2 (<strong>RC</strong>46W) only <strong>and</strong> the discharge<br />

valve of cylinder nr. 3 (<strong>RC</strong>46) or cylinder nr. 4<br />

(<strong>RC</strong>46W) to be always in communication with the<br />

permanent discharge chamber in the cylinder head<br />

cover <strong>and</strong> the common discharge chamber in the<br />

compressor housing.<br />

So, only this one cylinder nr. 3 (<strong>RC</strong>46) or cylinder nr.<br />

4 (<strong>RC</strong>46W) is always in operation, which has the<br />

extra advantage of also reducing the starting load<br />

from 50 to 25%.<br />

On special order, just by adding the symbol Z after<br />

the type designation, each st<strong>and</strong>ard compressor<br />

type can also be delivered without any capacity<br />

control. In that case not only one but all cylinder<br />

head covers are of the non-controllable type, i.e. not<br />

provided with built-in control piston <strong>and</strong> by-pass<br />

slide valve.<br />

However, the consequence of such a (cheaper)<br />

choice is that either fully loaded compressor<br />

3. DESCRIPTION AND OPERATION<br />

OF CAPACITY CONTROL<br />

starting has to be accepted, inevitably resulting in<br />

a more powerful electric motor to be installed, or<br />

special provisions are to be made by the installer<br />

in the field to overcome this inconvenience, for<br />

instance by applying an external line with solenoid<br />

valve (only open, so energized only during<br />

starting) between the suction <strong>and</strong> discharge line<br />

of the installation, combined with a non-return<br />

valve in the same discharge line.<br />

Important installation requirement!<br />

To prevent, during prolonged compressor<br />

st<strong>and</strong>-still, a gradual pressure equalisation<br />

between condenser <strong>and</strong> evaporator due to<br />

slow leakage of refrigerant gas via the<br />

slide valve, a non-return valve should all<br />

the times be mounted in the external<br />

discharge line.<br />

page C1.2 <strong>Installation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> <strong>RC</strong>(U)6 v001.99.01.en