<strong>Refrigeration</strong> Division<br />

Grasso<br />

FAULT CAUSE REMEDY<br />

A Discharge pressure too high 1. Discharge stop valve not fully open 1. Open fully<br />

2. Discharge pressure gauge defective 2. Renew<br />

3. Non condensables in system 3. Purge system with<br />

Grasso Automatic<br />

Purger<br />

B Discharge temperature too high 1. Discharge pressure too high 1. See A<br />

2. Too many cylinders cut out 2. Cut in more cylinders<br />

3. Suction pressure too low 3. See D<br />

4. Exessive superheat of suction gas 4. Eliminate exessive<br />

superheat<br />

5. Room temperature too high 5. Ventilate engine room<br />

better<br />

6. Discharge valve defective 6. Renew<br />

7. Pressure relief valve leaking 7. Renew<br />

C Suction pressure too high 1. Capacity control does not operate 1. Repair<br />

2. Compressor capacity too small 2. Consult installation<br />

engineer<br />

3. Suction pressure gauge defective 3. Repair or renew<br />

4. One or more suction valves defective 4. Repair or renew<br />

5. One or more discharge valves defective 5. Repair or renew<br />

6. Pressure relief valve is leaking 6. Renew<br />

D Suction pressure too low (suction<br />

pressure safety switch may<br />

possibly become operative)<br />

E Crankcase frosted or wet just after<br />

starting, possibly also during<br />

operation<br />

B: INSPECTION, MAINTENANCE<br />

AND TROUBLE SHOOTING<br />

1. Suction stop valve not fully open 1. Open fully<br />

2. Suction gas strainer polluted 2. Clean<br />

3. Too little refrigerant in installation 3. Top-up refrigerant<br />

4. Suction pressure gauge defective 4. Renew<br />

1. Liquid refrigerant in crankcase due to: In the case of big<br />

amount of refrigerant:<br />

stop compressor <strong>and</strong><br />

contact installation<br />

engineer<br />

1a. Room temperature too low 1a. See 1a<br />

1b. Return from oil separator mainly consists 1b. Contact installation<br />

of liquid refrigerant<br />

engineer<br />

1c. <strong>Installation</strong> operates too wet 1c. Re-adjust installation<br />

<strong>and</strong> provide for<br />

superheat<br />

1d. Liquid separator too small 1d. Contact installation<br />

engineer<br />

B1.8 <strong>Installation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> <strong>RC</strong>(U)6 v001.99.01.en