14.02.2013 Views

RC(U)6 Installation and Maintenance Manual - Marine Refrigeration ...

RC(U)6 Installation and Maintenance Manual - Marine Refrigeration ...

RC(U)6 Installation and Maintenance Manual - Marine Refrigeration ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Refrigeration</strong> Division<br />

Grasso<br />

4<br />

4<br />

A<br />

2<br />

A<br />

2<br />

Number of solenoid valves: 1 (A,)<br />

Number of control steps: 2<br />

B<br />

1<br />

1<br />

3<br />

Fig. 3.2 St<strong>and</strong>ard capacity control of compressor <strong>RC</strong>46<br />

Number of solenoid valves: 2 (A,B)<br />

Number of control steps: 4<br />

3<br />

Fig. 3.3 Alternative capacity control of compressor <strong>RC</strong>46<br />

3. DESCRIPTION AND OPERATION<br />

OF CAPACITY CONTROL<br />

solenoid valves energized<br />

- A �<br />

�<br />

Electrical<br />

control<br />

50 100 % Capacity<br />

No. of operating cylinders<br />

1 1<br />

- 2<br />

3 3<br />

- 4<br />

solenoid valves energized<br />

- - A A �<br />

- B - B<br />

�<br />

<strong>RC</strong>46<br />

(st<strong>and</strong>ard)<br />

Electrical<br />

control<br />

25* 50 75* 100 % Capacity<br />

No. of operating cylinders<br />

- 1 - 1<br />

- - 2 2<br />

3 3 3 3<br />

- - 4 4<br />

* Optional (see paragraph 3.5)<br />

<strong>RC</strong>46<br />

(alternative)<br />

page C1.4 <strong>Installation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> <strong>RC</strong>(U)6 v001.99.01.en