<strong>Refrigeration</strong> Division<br />

Grasso<br />

If an oil rectifier system is applied in the refrigeration<br />

system, the oil return line<br />

must be connected to the oil return connection.<br />

Never connect the oil rectifier return line to<br />

the suction line or to the suction gas filter.<br />

DO NOT ground through the compressor<br />

when arc welding<br />

Suspension of system pipework<br />

To eliminate vibration transmission to the system<br />

piping, the following is recommended:<br />

• Install all piping free of tension.<br />

• Secure the piping by clips or suspenders in two<br />

directions.<br />

• Install (stop) valves, piping <strong>and</strong> accessories such,<br />

that there is no load exerted on the compressor.<br />

A1.6 Connecting the power supply<br />

Before leaving the factory the compressor<br />

package is completely wired*. The connection to<br />

be made by the installer is between main power<br />

source <strong>and</strong> the Monitron CR (if ordered).<br />

Information about further electrical connections<br />

to be made (e.g. crankcase heater, drive motor<br />

starting equipment, thermal protection of drive<br />

motor, automatic start/ stop, motor current<br />

transducer <strong>and</strong> other external electrical devices)<br />

can be found in the order manual.<br />

* If the st<strong>and</strong>ard recommended Monitron CR is applied.<br />

A: INSTALLATION AND PREPARATION FOR USE<br />

A1.7 Earthing connections<br />

Grasso compressors <strong>and</strong> packages are equipped<br />

with litz-wires <strong>and</strong> earth connecting points.<br />

To avoid leakage current flowing through the<br />

components, disconnect all litz-wires when arcwelding.<br />

After all installation functions are<br />

completed, reconnect the litz-wires <strong>and</strong> ground<br />

the package to earth.<br />

A1.8 Separately delivered components<br />

Mount the separately delivered set-components<br />

e.g. oil charge <strong>and</strong> drain valve, according to the<br />

instruction enclosed in each individual set.<br />

A1.6 <strong>Installation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> <strong>RC</strong>(U)6 v001.99.01.en