Remanent Data<br />

4.8.2 Extraremanent Data Range<br />

Prerequisite: Ventura Remote PLC DP:<br />

Target and LZS version 02030207<br />

Ventura Remote PLC CAN:<br />

Target and LZS version 02030106<br />

To avoid the transfer of a program provoking the loss of<br />

important data or data it took a lot of effort to enter, a<br />

NVRAM area of 8 or 12 Kbytes was provided for safekeeping<br />

data that the system will not delete at any time.<br />

To keep things simple, these data are referred to as<br />

"extraremanent data".<br />

Controller Address Range<br />

Ventura SlotPLC 8 Kbytes<br />

PCControl 645-12M-<br />

PCI-CoDeSys<br />

Ventura Remote<br />

PLC<br />

8 Kbytes<br />

from 16#404000<br />

to 16#405FFF<br />

from 16#1F4000<br />

to 16#1F5FFF<br />

12 from 16#204000<br />

Kbytes to 16#206FFF<br />

Data management of these data is entirely subject to the<br />

user's responsibility.<br />

� The extraremanent memory range is appended as a<br />

subelement to the PLC configuration.<br />

� This range is addressed by global variable "xrdata".<br />

� The data type of "xrdata" is "XREMDATA". This data<br />

type is specified by its name only. Its contents is to be<br />

defined by the programmer with regard to the<br />

application (see example below).<br />