17.02.2013 Views

Kuhnke Electronics Instruction Manual

Kuhnke Electronics Instruction Manual

Kuhnke Electronics Instruction Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

PROFIBUS<br />

replaces the term "byte" with the term "octet" which is also<br />

the word used by the standard.<br />

A set bit (=1) signifies that the described event has<br />

occurred.<br />

6.2.3.1 Standard Diagnostic Data<br />

Bit set by Explanation<br />

Octet 1: station_status_1<br />

0 master Diag.Station_Non_Existent (not supported by <strong>Kuhnke</strong> masters)<br />

DP slave cannot be accessed via the bus<br />

1 slave Diag.Station_Not_Ready<br />

DP slave not ready for data exchange<br />

2 slave Diag.Cfg_Fault<br />

The last set of configuration data received from the master is<br />

not the same that the DP slave found<br />

3 slave Diag.Ext_Diag<br />

There is a device-specific diagnostic result (octet 7...)<br />

4 slave Diag.Not_Supported<br />

The requested information cannot be supplied by the DP slave<br />

5 master Diag.Invalid_Slave_Response<br />

The slave response is not plausible<br />

6 slave Diag.Param_Fault<br />

Bad telegram of parameter data sent<br />

7 master Diag.Master_Lock<br />

The DP slave parameters were set by another master<br />

161

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!