PROFIBUS<br />
replaces the term "byte" with the term "octet" which is also<br />
the word used by the standard.<br />
A set bit (=1) signifies that the described event has<br />
occurred.<br />
6.2.3.1 Standard Diagnostic Data<br />
Bit set by Explanation<br />
Octet 1: station_status_1<br />
0 master Diag.Station_Non_Existent (not supported by <strong>Kuhnke</strong> masters)<br />
DP slave cannot be accessed via the bus<br />
1 slave Diag.Station_Not_Ready<br />
DP slave not ready for data exchange<br />
2 slave Diag.Cfg_Fault<br />
The last set of configuration data received from the master is<br />
not the same that the DP slave found<br />
3 slave Diag.Ext_Diag<br />
There is a device-specific diagnostic result (octet 7...)<br />
4 slave Diag.Not_Supported<br />
The requested information cannot be supplied by the DP slave<br />
5 master Diag.Invalid_Slave_Response<br />
The slave response is not plausible<br />
6 slave Diag.Param_Fault<br />
Bad telegram of parameter data sent<br />
7 master Diag.Master_Lock<br />
The DP slave parameters were set by another master<br />
161