Software<br />

5.4 Functions of the Basic Module's Inputs and<br />

Outputs<br />

5.4.1 Functions of Inputs SDE_0...SDE_1 (SDE_3)<br />

The 16 (or 32) inputs of the basic module are normal<br />

inputs without any special function.<br />

5.4.2 Functions of Outputs SDO_0... SD0_1 (SD0_3)<br />

The 16 (or 32) outputs of the basic module are normal<br />

outputs without any special function.<br />

A short-circuited output is not turned off by the PLC.<br />

Overload simply fuses out the outputs thermally. You are<br />

advised to provide means of preventing the output from<br />

turning back on after cooling down.<br />

The short-circuited output generates an interrupt request.<br />

To allocate program code to the interrupt request run<br />

function INSTALL_ERROR_IRQ<br />

(� 4.4.6)<br />

The module should contain the code to respond to the<br />

request, e.g. to turn off some major or all outputs using<br />

function ENADIS_OUTPUTS (� 4.4.3)<br />

149