Annexe 1<br />

Extrait <strong>de</strong> la Norme ASHRAE 62-2001 sur les fréqu<strong>en</strong>ces d’<strong>en</strong>treti<strong>en</strong> recommandées<br />

Référ<strong>en</strong>ce : ANSI/ASHRAE STANDARD 62-2001, page 16<br />

Filters and air cleaning <strong>de</strong>vices<br />

Outdoor air dampers and actuators<br />

Humidifiers<br />

Dehumidification coils<br />

Drain pans and other adjac<strong>en</strong>t surfaces subject to wetting<br />

Outdoor air intake louvers, bird scre<strong>en</strong>s, mist eliminators, and adjac<strong>en</strong>t areas<br />

S<strong>en</strong>sors used for dynamic minimum outdoor air control<br />

Air-handling systems except for units un<strong>de</strong>r 1000 L/s (2000 cfm)<br />

Cooling towers<br />

Floor drains located in pl<strong>en</strong>ums or rooms that serve as air pl<strong>en</strong>ums<br />

Equipm<strong>en</strong>t/compon<strong>en</strong>t accessibility<br />

Visible microbial contamination<br />

Water intrusion or accumulation<br />

ITEM ACTIVITY MINIMUM FREQUENCY<br />

A According to O & M Manual<br />

ACTIVITY CODE:<br />

A Maintain according to O & M Manual.<br />

B Visually inspect of remotely monitor for proper function.<br />

C Clean and maintain to limit fouling and microbial growth.<br />

D Visually inspect for cleanliness and microbial growth and clean wh<strong>en</strong> fouling is observed.<br />

E Visually inspect for cleanliness and integrity and clean wh<strong>en</strong> necessary.<br />

F Verify accuracy and recalibrate or replace as necessary.<br />

B<br />

C<br />

D<br />

D<br />

E<br />

F<br />

G<br />

H<br />

I<br />

J<br />

K<br />

K<br />

50<br />

Every three months or in accordance with O & M Manual<br />

Every three months of use or in accordance with O & M Manual<br />

Regularly wh<strong>en</strong> it is likely that <strong>de</strong>humidification occurs but no less than once<br />

per year or as specified in the O & M Manual<br />

Once per year during cooling season or as specified in the O & M Manual<br />

Every six months or as specified in the O & M Manual<br />

Every six months or periodically in accordance with O & M Manual<br />

Once every five years<br />

In accordance with O & M Manual or treatm<strong>en</strong>t system provi<strong>de</strong>r<br />

Periodically according to O & M Manual<br />

G Measure minimum quantity of outdoor air. If measured minimum air flow rates are less<br />

than 90% of the minimum outdoor air rate in the O & M Manual, they shall be adjusted<br />

or modified to bring them above 90% or shall be evaluated to <strong>de</strong>termine if the measured<br />

rates are in conformance with this standard.<br />

H Treat to limit the growth of microbiological contaminants.<br />

I Maintain to prev<strong>en</strong>t transport of contaminants from the floor drain to the pl<strong>en</strong>um.<br />

J Keep clear the space provi<strong>de</strong>d for routine maint<strong>en</strong>ance and inspection around <strong>v<strong>en</strong>tilation</strong><br />

equipm<strong>en</strong>t.<br />

K Investigate and rectify.<br />

* Minimum frequ<strong>en</strong>cies may be increased or <strong>de</strong>creased if indicated in the O & M Manual.