5. Setting of volumetric flows for hydraulic calibration MC/UC<br />

Requirements for the presetting of both volumetric flows<br />

1. All radiator valves and e.g. under floor heating have to be set at the maximum flow-rate.<br />

2. Mixer at <strong>Thermix</strong> is fully opened (no admixing), bypass is closed.<br />

3. Pump at <strong>Thermix</strong> is activated.<br />

4. Wall mounted boiler is in operation.<br />

The required volumetric flow for the unmixed and mixed circuit, as well as the required pump levels at the boiler and <strong>Thermix</strong> pump is to be<br />

taken from the attached table according to heat requirement. The flow rate at the individual flow rate gauges is to be adjusted as follows:<br />

1. Adjust the determined pump levels at the boiler and <strong>Thermix</strong> pump.<br />

2. Adjust the determined volumetric flow of the under floor heating by means of the alignment valve.<br />

3. Fine adjustment takes place with both alignment valves until the quoted volumetric flows are reached.<br />

If a higher heat requirement of the mixer circuit is required, the <strong>Thermix</strong> pump is to be adjusted to the higher<br />

level and the calibration has to be performed once more. All changes in the heating circuit heat requirement (e.g. enlargement of the heating<br />

floor surface) require another adjustment in the volumetric flow.<br />

With assembly and operational all valid norms and regulationsare to be followed and observed!<br />

see Fig. 7 A Under floor heating B <strong>Thermix</strong> C Flow indicator alignment valve<br />

D Wall boiler E Flow indicator<br />

alignment valve<br />

F Heating element circuit<br />

Connection example of an unmixed and a mixed heating circuit with <strong>Thermix</strong>. Two flow rate limiters with display are used to set the required<br />

volumetric flows for both heating circuits.