5. Setting of volumetric flows for hydraulic calibration MC/UC<br />
Requirements for the presetting of both volumetric flows<br />
1. All radiator valves and e.g. under floor heating have to be set at the maximum flow-rate.<br />
2. Mixer at <strong>Thermix</strong> is fully opened (no admixing), bypass is closed.<br />
3. Pump at <strong>Thermix</strong> is activated.<br />
4. Wall mounted boiler is in operation.<br />
The required volumetric flow for the unmixed and mixed circuit, as well as the required pump levels at the boiler and <strong>Thermix</strong> pump is to be<br />
taken from the attached table according to heat requirement. The flow rate at the individual flow rate gauges is to be adjusted as follows:<br />
1. Adjust the determined pump levels at the boiler and <strong>Thermix</strong> pump.<br />
2. Adjust the determined volumetric flow of the under floor heating by means of the alignment valve.<br />
3. Fine adjustment takes place with both alignment valves until the quoted volumetric flows are reached.<br />
If a higher heat requirement of the mixer circuit is required, the <strong>Thermix</strong> pump is to be adjusted to the higher<br />
level and the calibration has to be performed once more. All changes in the heating circuit heat requirement (e.g. enlargement of the heating<br />
floor surface) require another adjustment in the volumetric flow.<br />
With assembly and operational all valid norms and regulationsare to be followed and observed!<br />
see Fig. 7 A Under floor heating B <strong>Thermix</strong> C Flow indicator alignment valve<br />
D Wall boiler E Flow indicator<br />
alignment valve<br />
F Heating element circuit<br />
Connection example of an unmixed and a mixed heating circuit with <strong>Thermix</strong>. Two flow rate limiters with display are used to set the required<br />
volumetric flows for both heating circuits.