Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
21<br />
Guideline value table for the presetting of the heating system with <strong>Thermix</strong><br />
Boiler circuit<br />
preliminary<br />
heat<br />
temperature<br />
unmixed<br />
heating circuit<br />
(°C)<br />
Preliminary<br />
heat<br />
temperature<br />
mixed<br />
heating circuit<br />
(°C)<br />
Spread for<br />
mixed<br />
heating<br />
circuit<br />
(K)<br />
Pressure<br />
loss mixed<br />
heating<br />
circuit<br />
(bar)<br />
pump setting of<br />
<strong>Thermix</strong>pumpe<br />
necessary volumetric flow of<br />
the boiler circuit<br />
(I/h)<br />
necessary pressure difference<br />
before <strong>Thermix</strong><br />
(from the boiler circuit)<br />
(bar)<br />
Achievement mixed heating circle (kW) 5 10 15 20 5 10 15 20 5 10 15 20<br />
65<br />
25<br />
30<br />
35<br />
40<br />
45<br />
50<br />
3<br />
5<br />
5<br />
7<br />
5<br />
7<br />
7<br />
10<br />
10<br />
15<br />
15<br />
20<br />
0.10 3 - - - 102 - - - 0.01 - - -<br />
0.15 3 - - - 102 - - - 0.01 - - -<br />
0.20 3 - - - 102 - - - 0.01 - - -<br />
0.10 1 3 - - 97 195 - - 0.01 0.02 - -<br />
0.15 2 3 - - 97 195 - - 0.01 0.02 - -<br />
0.20 2 - - - 97 - - - 0.01 - - -<br />
0.10 1 3 - - 110 219 - - 0.01 0.02 - -<br />
0.15 2 3 - - 110 219 - - 0.01 0.02 - -<br />
0.20 2 - - - 110 - - - 0.01 - - -<br />
0.10 1 2 3 - 104 209 313 - 0.01 0.02 0.07 -<br />
0.15 1 3 - - 104 209 - - 0.01 0.02 - -<br />
0.20 2 3 - - 104 209 - - 0.01 0.02 - -<br />
0.10 1 3 - - 125 251 - - 0.01 0.04 - -<br />
0.15 2 3 - - 125 251 - - 0.01 0.04 - -<br />
0.20 2 - - - 125 - - - 0.01 - -<br />
0.10 1 2 3 - 119 237 356 - 0.01 0.03 0.09 -<br />
0.15 1 3 - - 119 237 - - 0.01 0.03 - -<br />
0.20 2 3 - - 119 237 - - 0.01 0.03 - -<br />
0.10 1 2 3 - 137 274 411 - 0.01 0.05 0.13 -<br />
0.15 1 3 - - 137 274 - - 0.01 0.05 - -<br />
0.20 2 3 - - 137 274 - - 0.01 0.05 - -<br />
0.10 1 1 3 3 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.15 1 2 3 3 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.20 1 2 3 - 125 251 376 - 0.01 0.04 0.11 -<br />
0.10 1 1 3 3 146 292 438 585 0.01 0.06 0.15 0.31<br />
0.15 1 2 3 3 146 292 438 585 0.01 0.06 0.15 0.31<br />
0.20 1 2 3 - 146 292 438 - 0.01 0.06 0.15 -<br />
0.10 1 1 1 2 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.15 1 1 2 2 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.20 1 1 2 3 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.10 1 1 1 2 146 292 438 585 0.01 0.06 0.15 0.31<br />
0.15 1 1 2 2 146 292 438 585 0.01 0.06 0.15 0.31<br />
0.20 1 1 2 3 146 292 438 585 0.01 0.06 0.15 0.31<br />
0.10 1 1 1 1 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.15 1 1 1 2 125 251 376 501 0.01 0.04 0.11 0.21<br />
0.20 1 1 2 2 125 251 376 501 0.01 0.04 0.11 0.21<br />
All data are guideline values; depending on the system, deviations can occur = <strong>Thermix</strong> cannot be used. Guide-value tables for deviating<br />
supply water temperatures, spreads and pressure losses can be supplied on request.