Annex 1<br />
The application of the calculation procedure <strong>is</strong> demonstrated in 8.5.<br />
42<br />
Maximum values Guide values<br />
R/X kPmax system kP validity r<strong>an</strong>ge<br />
< 0.1 0.45 For d ≤ 40 mm with equip-<br />
0.1 0.43 L.V. 0.22…0.27 ment near to tr<strong>an</strong>sformer;<br />
0.2 0.38 (≤ 1000 V) For d ≤ 70 mm with<br />
0.5 0.33 equipment near to end-use<br />
1.0 0.29<br />
2.0 0.26 M.V. 0.04…0.10<br />
≥ 0.2 0.25 (> 1000 V)<br />
Tab. A1.1: Maximum <strong>an</strong>d guide values of the normalized <strong>arc</strong> power