127083-Y<strong>IM</strong>-B-0606<br />
Excessive exposure of this furnace to contaminated<br />
combustion air may result in equipment damage or<br />
personal injury. Typical contaminates include: permanent<br />
wave solution, chlorinated waxes <strong>and</strong> cleaners,<br />
chlorine based swimming pool chemicals, water<br />
softening chemicals, carbon tetrachloride, Halogen<br />
type refrigerants, cleaning solvents (e.g. perchloroethylene),<br />
printing inks, paint removers, varnishes,<br />
hydrochloric acid, cements <strong>and</strong> glues, antistatic fabric<br />
softeners for clothes dryers, masonry acid washing<br />
materials.<br />
RIGGING AND HANDLING<br />
Exercise care when moving the unit. Do not remove any<br />
packaging until the unit is near the place of installation. Rig<br />
the unit by attaching chain or cable slings to the lifting holes<br />
provided in the base rails. Spreader bars, whose length<br />
exceeds the largest dimension across the unit, MUST be<br />
used across the top of the unit.<br />
If a unit is to be installed on a roof curb other than a<br />
YORK roof curb, gasketing must be applied to all<br />
surfaces that come in contact with the unit underside.<br />
Before lifting, make sure the unit weight is distributed<br />
equally on the rigging cables so it will lift evenly.<br />
<strong>Units</strong> may be moved or lifted with a forklift. Slotted openings<br />
in the base rails are provided for this purpose.<br />
LENGTH OF FORKS MUST BE A MIN<strong>IM</strong>UM OF 60<br />
INCHES.<br />
All panels must be secured in place when the unit is<br />
lifted.<br />
The condenser coils should be protected from rigging<br />
cable damage with plywood or other suitable<br />
material.<br />
TABLE 3: UNIT WEIGHT<br />
Unitary Products Group 11<br />
Model<br />
Shipping 1<br />
Weight (lbs.)<br />
1. Weights include largest heating option.<br />
2.<br />
8 tube gas section.<br />
3. 54kW heater.<br />
Operating<br />
Weight (lbs.)<br />
DF078 1058 1053<br />
DF090 875 870<br />
DF102 888 883<br />
DF120 1190 1185<br />
ECON. 85 84<br />
PE 150 148<br />
GAS HEAT 2<br />
110 100<br />
ELEC. HEAT3 49 49<br />
FIGURE 5 - UNIT 4 POINT LOAD<br />
TABLE 4: 4 POINT LOAD WEIGHT<br />
Model<br />
)<br />
- . 6<br />
Location (lbs.) 1<br />
A B C D<br />
DF078 231 197 288 337<br />
DF090 195 146 228 306<br />
DF102 197 147 230 309<br />
DF120 260 222 324 379<br />
1. Weights include largest heating option.<br />
TABLE 5: 6 POINT LOAD WEIGHT<br />
,<br />
Location (lbs.)<br />
Model<br />
A B C D E F<br />
DF078 158 142 128 187 207 231<br />
DF090 137 112 93 145 175 214<br />
DF102 138 113 93 146 175 216<br />
DF120 178 160 144 210 233 260<br />
*<br />
. 4 6<br />
+