SECOND STAGE OF HEATING<br />

When the ICB receives a call for the second stage of heating,<br />

“W2,” the ICB conducts a complete first stage ignition<br />

sequence. If this sequence is satisfied, the second main<br />

valve of the GV is opened.<br />

When “W2” is satisfied, the second main valve is closed.<br />

RETRY OPERATION<br />

When a flame is lost or is not detected during an attempt to<br />

achieve ignition, a retry operation occurs. A 30-second purge<br />

is performed between ignition attempts.<br />

If the unit fails after three ignition attempts, the furnace is<br />

locked-out for one hour. The furnace is monitored during this<br />

one-hour period for unsafe conditions.<br />

RECYCLE OPERATION<br />

When a flame is lost after the flame stabilization period, a<br />

recycle operation occurs. If the unit fails after five recycle<br />

attempts, the furnace is locked-out for one hour.<br />

GAS HEATING OPERATION ERRORS<br />

LOCK-OUT<br />

A one-hour lockout occurs following three retries or five recycles.<br />

During the one-hour lockout, flame detection, limit conditions,<br />

<strong>and</strong> main valves are tested. Any improper results will<br />

cause the appropriate action to occur. Recycling the low voltage<br />

power cancels the lock-out.<br />

TEMPERATURE L<strong>IM</strong>IT<br />

If the UCB senses zero volts from the high temperature limit,<br />

the indoor blower motor is immediately energized. When the<br />

UCB again senses 24 volts from the temperature limit, the<br />

draft motor will perform a 15-second post-purge <strong>and</strong> the<br />

indoor blower will be de-energized following the elapse of the<br />

fan off delay for heating.<br />

This limit is monitored regardless of unit operation status, i.e.<br />

this limit is monitored at all times.<br />

If the temperature limit opens three times within one hour, it<br />

will lock-on the indoor blower motor <strong>and</strong> flash code is initiated<br />

(See Table 54).<br />

FLAME SENSE<br />

Flame sensing occurs at all times. If “W1” is not present <strong>and</strong><br />

a flame is sensed for 2 seconds, the draft motor is energized<br />

<strong>and</strong> the GV is kept off. The ICB halts any operation until a<br />

flame is not detected. Once the flame detection is lost, the<br />

ICB performs a post-purge. Normal operation is allowed concurrently<br />

with the purge (i.e. this purge can be considered the<br />

purge associated with a call for “W1”).<br />

127083-Y<strong>IM</strong>-B-0606<br />

If “W1” is present, a flame is sensed, but the GV is not energized,<br />

the draft motor is energized until the flame detection is<br />

lost. Normal operation is now allowed.<br />

The flame detection circuitry continually tests itself. If the ICB<br />

finds the flame detection circuitry to be faulty, the ICB will not<br />

permit an ignition sequence <strong>and</strong> the draft motor is energized.<br />

If this failure should occur during an ignition cycle the failure<br />

is counted as a recycle.<br />

GAS VALVE<br />

The UCB <strong>and</strong> ICB continuously monitor the GV.<br />

If the ICB senses voltage at the GV when not requested, the<br />

ICB will energize the draft motor. The ICB will not operate the<br />

furnace until voltage is no longer sensed at the GV. The draft<br />

motor is stopped when voltage is not sensed at the GV.<br />

Any time the UCB senses voltage at the GV without a call for<br />

heat for a continuous five-minute period, the UCB will lock-on<br />

the indoor blower <strong>and</strong> a flash code is initiated (Table 54).<br />

When voltage is no longer sensed at the GV, the UCB will deenergize<br />

the indoor blower following the elapse of the fan off<br />

delay for heating.<br />

If voltage has been sensed at the GV for at least 15 seconds<br />

during the fan on delay for heating <strong>and</strong> GV voltage or “W1” is<br />

lost, the indoor blower is forced on for the length of the fan off<br />

delay for heating.<br />

During a call for heat, if the UCB does not sense voltage at<br />

the GV for a continuous five-minute period the UCB will initiate<br />

a flash code (Table 54). The indoor blower motor will not<br />

be locked-on while there is no GV voltage.<br />

SAFETY CONTROLS<br />

The UCB monitors the temperature limit switch of gas heat<br />

units.<br />

The control circuit includes the following safety controls:<br />

L<strong>IM</strong>IT SWITCH (LS)<br />

This control is located inside the gas heat compartment <strong>and</strong><br />

is set to open at the temperature indicated in the <strong>Gas</strong> Heat<br />

Limit Control Settings Table 46. It resets automatically. The<br />

limit switch operates when a high temperature condition,<br />

caused by inadequate supply air flow occurs, thus shutting<br />

down the heater <strong>and</strong> energizing the blower.<br />

AUXILIARY L<strong>IM</strong>IT SWITCH (ALS)<br />

This control is located inside the supply air compartment <strong>and</strong><br />

is set to open at the temperature indicated in the <strong>Gas</strong> Heat<br />

Limit Control Settings Table 46. It resets manually. The limit<br />

switch operates when a high temperature condition, caused<br />

52 Unitary Products Group