SECOND STAGE OF HEATING<br />
When the ICB receives a call for the second stage of heating,<br />
“W2,” the ICB conducts a complete first stage ignition<br />
sequence. If this sequence is satisfied, the second main<br />
valve of the GV is opened.<br />
When “W2” is satisfied, the second main valve is closed.<br />
RETRY OPERATION<br />
When a flame is lost or is not detected during an attempt to<br />
achieve ignition, a retry operation occurs. A 30-second purge<br />
is performed between ignition attempts.<br />
If the unit fails after three ignition attempts, the furnace is<br />
locked-out for one hour. The furnace is monitored during this<br />
one-hour period for unsafe conditions.<br />
RECYCLE OPERATION<br />
When a flame is lost after the flame stabilization period, a<br />
recycle operation occurs. If the unit fails after five recycle<br />
attempts, the furnace is locked-out for one hour.<br />
GAS HEATING OPERATION ERRORS<br />
LOCK-OUT<br />
A one-hour lockout occurs following three retries or five recycles.<br />
During the one-hour lockout, flame detection, limit conditions,<br />
<strong>and</strong> main valves are tested. Any improper results will<br />
cause the appropriate action to occur. Recycling the low voltage<br />
power cancels the lock-out.<br />
TEMPERATURE L<strong>IM</strong>IT<br />
If the UCB senses zero volts from the high temperature limit,<br />
the indoor blower motor is immediately energized. When the<br />
UCB again senses 24 volts from the temperature limit, the<br />
draft motor will perform a 15-second post-purge <strong>and</strong> the<br />
indoor blower will be de-energized following the elapse of the<br />
fan off delay for heating.<br />
This limit is monitored regardless of unit operation status, i.e.<br />
this limit is monitored at all times.<br />
If the temperature limit opens three times within one hour, it<br />
will lock-on the indoor blower motor <strong>and</strong> flash code is initiated<br />
(See Table 54).<br />
FLAME SENSE<br />
Flame sensing occurs at all times. If “W1” is not present <strong>and</strong><br />
a flame is sensed for 2 seconds, the draft motor is energized<br />
<strong>and</strong> the GV is kept off. The ICB halts any operation until a<br />
flame is not detected. Once the flame detection is lost, the<br />
ICB performs a post-purge. Normal operation is allowed concurrently<br />
with the purge (i.e. this purge can be considered the<br />
purge associated with a call for “W1”).<br />
127083-Y<strong>IM</strong>-B-0606<br />
If “W1” is present, a flame is sensed, but the GV is not energized,<br />
the draft motor is energized until the flame detection is<br />
lost. Normal operation is now allowed.<br />
The flame detection circuitry continually tests itself. If the ICB<br />
finds the flame detection circuitry to be faulty, the ICB will not<br />
permit an ignition sequence <strong>and</strong> the draft motor is energized.<br />
If this failure should occur during an ignition cycle the failure<br />
is counted as a recycle.<br />
GAS VALVE<br />
The UCB <strong>and</strong> ICB continuously monitor the GV.<br />
If the ICB senses voltage at the GV when not requested, the<br />
ICB will energize the draft motor. The ICB will not operate the<br />
furnace until voltage is no longer sensed at the GV. The draft<br />
motor is stopped when voltage is not sensed at the GV.<br />
Any time the UCB senses voltage at the GV without a call for<br />
heat for a continuous five-minute period, the UCB will lock-on<br />
the indoor blower <strong>and</strong> a flash code is initiated (Table 54).<br />
When voltage is no longer sensed at the GV, the UCB will deenergize<br />
the indoor blower following the elapse of the fan off<br />
delay for heating.<br />
If voltage has been sensed at the GV for at least 15 seconds<br />
during the fan on delay for heating <strong>and</strong> GV voltage or “W1” is<br />
lost, the indoor blower is forced on for the length of the fan off<br />
delay for heating.<br />
During a call for heat, if the UCB does not sense voltage at<br />
the GV for a continuous five-minute period the UCB will initiate<br />
a flash code (Table 54). The indoor blower motor will not<br />
be locked-on while there is no GV voltage.<br />
SAFETY CONTROLS<br />
The UCB monitors the temperature limit switch of gas heat<br />
units.<br />
The control circuit includes the following safety controls:<br />
L<strong>IM</strong>IT SWITCH (LS)<br />
This control is located inside the gas heat compartment <strong>and</strong><br />
is set to open at the temperature indicated in the <strong>Gas</strong> Heat<br />
Limit Control Settings Table 46. It resets automatically. The<br />
limit switch operates when a high temperature condition,<br />
caused by inadequate supply air flow occurs, thus shutting<br />
down the heater <strong>and</strong> energizing the blower.<br />
AUXILIARY L<strong>IM</strong>IT SWITCH (ALS)<br />
This control is located inside the supply air compartment <strong>and</strong><br />
is set to open at the temperature indicated in the <strong>Gas</strong> Heat<br />
Limit Control Settings Table 46. It resets manually. The limit<br />
switch operates when a high temperature condition, caused<br />
52 Unitary Products Group