TABLE 22: DF078 (6-1/2 TON) STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE<br />
ESP 3<br />
TURNS OPEN 4<br />
0 1 2 3 4 5<br />
CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP<br />
0.2 - - - - - - 3291 1191 1.28 3096 1059 1.14 2963 948 1.02 2757 831 0.89<br />
0.4 - - - 3168 1225 1.31 2969 1085 1.16 2658 939 1.01 2535 834 0.89 2255 718 0.77<br />
0.6 3223 1273 1.37 2732 1084 1.16 2500 947 1.02 2110 803 0.86 1923 699 0.75 1608 596 0.64<br />
0.8 2541 1091 1.17 2168 925 0.99 1882 793 0.85 - - - - - - - - -<br />
1.0 1859 908 0.97 - - - - - - - - - - - - - - -<br />
1. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.<br />
2. Blower performance includes two-inch throwaway filters.<br />
3. ESP (External Static Pressure) given is that available for the supply <strong>and</strong> return air duct system. All internal resistances have been<br />
deducted from the total static pressure of the blower.<br />
4. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.<br />
5. W = Watts<br />
1 2<br />
TABLE 23: DF078 (6-1/2 TON) OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE<br />
ESP 3<br />
TURNS OPEN 4<br />
0 1 2 3 4 5<br />
CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP<br />
0.4 - - - - - - - - - - - - - - - 3489 1553 1.67<br />
0.6 - - - - - - - - - - - - 3394 1641 1.76 3101 1407 1.51<br />
0.8 - - - - - - 3623 2009 2.15 3323 1742 1.87 2971 1477 1.58 2607 1241 1.33<br />
1.0 - - - 3643 2150 2.31 3224 1820 1.95 2889 1569 1.68 2466 1306 1.40 2009 1071 1.15<br />
1.2 3613 2238 2.40 3143 1917 2.06 2748 1621 1.74 2369 1385 1.49 1879 1141 1.22 - - -<br />
1.4 3099 2039 2.19 2636 1711 1.83 2195 1424 1.53 - - - - - - - - -<br />
1.6 2586 1833 1.97 2124 1532 1.64 - - - - - - - - - - - -<br />
1.8 2073 1621 1.74 - - - - - - - - - - - - - - -<br />
1. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.<br />
2. Blower performance includes two-inch throwaway filters.<br />
3.<br />
ESP (External Static Pressure) given is that available for the supply <strong>and</strong> return air duct system. All internal resistances have been<br />
deducted from the total static pressure of the blower.<br />
4. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.<br />
5. W = Watts<br />
Unitary Products Group 31