127083-Y<strong>IM</strong>-B-0606<br />

4-1/4<br />

30-11/32<br />

FIGURE 8 - UNIT D<strong>IM</strong>ENSIONS<br />

X<br />

LEFT<br />

59<br />

Power<br />

Entry<br />

Ø 2-1/2<br />

30-3/16<br />

17-3/16<br />

24-3/16 6-3/16<br />

TABLE 6: UNIT HEIGHT<br />

Unit Model Number X<br />

DF078 50 3/4<br />

DF090 42<br />

DF102 42<br />

DF120 50 3/4<br />

TABLE 7: UNIT CLEARANCES<br />

Top 1<br />

Front 2<br />

Rear 3<br />

1. <strong>Units</strong> must be installed outdoors. Overhanging structure<br />

or shrubs should not obstruct condenser air discharge<br />

outlet.<br />

2. The products of combustion must not be allowed to<br />

accumulate within a confined space <strong>and</strong> re-circulate.<br />

3. To remove the slide-out drain pan, a rear clearance of<br />

sixty inches is required. If space is unavailable, the<br />

drain pan can be removed through the front by separating<br />

the corner wall.<br />

4. <strong>Units</strong> may be installed on combustible floors made from<br />

wood or class A, B or C roof covering materials.<br />

DETAIL A<br />

# "<br />

72” Right 12”<br />

36” Left 36”<br />

36” Bottom 4<br />

/ = I 2 EF A 1 A J<br />

% ! $<br />

8 EA M B 9 = ) ? H I I BH + E<br />

* = I A<br />

2 = <br />

0”<br />

Control<br />

Entry<br />

Ø 7/8<br />

Power<br />

Entry<br />

Ø 2-1/2<br />

Convenience<br />

Power<br />

Outlet<br />

Entry<br />

Ø 7/8<br />

27<br />

For Drain<br />

Dimensions<br />

See Detail C<br />

89<br />

See Detail<br />

A<br />

For Baserail<br />

Dimensions<br />

See Detail B<br />

NOTE: A one-inch clearance must be provided between<br />

any combustible material <strong>and</strong> the supply ductwork<br />

for a distance of 3 feet from the unit.<br />

DETAIL B<br />

DETAIL C<br />

NOTE: If the unit includes gas heating, locate the unit so<br />

the flue exhaust is at least:<br />

• Three (3) feet above any forced air inlet located within 10<br />

horizontal feet (excluding those integral to the unit).<br />

• Four (4) feet below, four (4) horizontal feet from, or one<br />

(1) foot above any door or gravity air inlet into the building.<br />

• Four (4) feet from electric meters, gas meters, regulators,<br />

<strong>and</strong> relief equipment.<br />

Unitary Products Group 13<br />

FRONT<br />

# ! &<br />

! ! "<br />

! &<br />

11-1/2<br />

! ' $