127083-Y<strong>IM</strong>-B-0606<br />
pipe dope must be used when assembling wrought iron or<br />
steel pipe for LP. Shellac base compounds such as <strong>Gas</strong>kolac<br />
or Stalastic, <strong>and</strong> compounds such as Rectorseal #5, Clyde’s,<br />
or John Crane may be used.<br />
Check all connections for leaks when piping is completed<br />
using a soap solution. NEVER USE A FLAME.<br />
FIRE OR EXPLOSION HAZARD<br />
Failure to follow the safety warning exactly could<br />
result in serious injury, death or property damage.<br />
Never test for gas leaks with an open flame. use a<br />
commercially available soap solution made specifically<br />
for the detection of leaks to check all connections.<br />
A fire or explosion may result causing property<br />
damage, personal injury or loss of life.<br />
VENT AND COMBUSTION AIR<br />
Venting slots in the heating compartment access panel<br />
remove the need for a combustion air hood. The gas heat<br />
flue exhaust is routed through factory installed exhaust piping<br />
with screen. If necessary, a flue exhaust extension may be<br />
installed at the point of installation.<br />
OPTIONS/<strong>AC</strong>CESSORIES<br />
ELECTRIC HEAT<br />
<strong>Electric</strong> heaters are available as factory-installed options or<br />
field-installed accessories. Refer to electric heat instructions<br />
for installation. These heaters mount in the heat compartment<br />
with the heating elements extending into the supply air chamber.<br />
All electric heaters are fused <strong>and</strong> intended for use with<br />
single point power supply.<br />
MOTORIZED OUTDOOR DAMPER<br />
The Motorized Outdoor Damper can be a factory installed<br />
option or a field installed accessory. If factory installed, refer<br />
to the instructions included with the outdoor air hood to complete<br />
the assembly. Field installed Motorized Outdoor<br />
Damper accessories include complete instructions for installation.<br />
ECONOMIZER<br />
The Economizer can be a factory installed option or a field<br />
installed accessory. If factory installed, refer to the instructions<br />
included with the outdoor air hood to complete the<br />
assembly. Field installed Economizer accessories include<br />
complete instructions for installation.<br />
There are two Economizer options:<br />
1. Down Flow application with barometric relief hood st<strong>and</strong>ard.<br />
2. Horizontal Flow application that requires the purchase of<br />
a barometric relief hood.<br />
POWER EXHAUST<br />
The Power Exhaust can be a factory installed option or a field<br />
installed accessory. If factory installed, refer to the instructions<br />
included with the outdoor air hood to complete the<br />
assembly. Field installed Power Exhaust accessories include<br />
complete instructions for installation.<br />
The Power Exhaust factory installed option is for Down Flow<br />
application only.<br />
There are two field installed Power Exhaust accessories:<br />
1. Down Flow application.<br />
2. Horizontal Flow application that requires the purchase of<br />
a barometric relief hood.<br />
RAIN HOOD<br />
All of the hood components, including the filters, the gasketing<br />
<strong>and</strong> the hardware for assembling, are packaged <strong>and</strong><br />
located between the condenser coil section <strong>and</strong> the main unit<br />
cabinet, if the unit has factory installed options. If field<br />
installed accessories are being installed all parts necessary<br />
for the installation comes in the accessory.<br />
ECONOMIZER AND POWER EXHAUST SET POINT<br />
ADJUSTMENTS AND INFORMATION<br />
Remove the top rear access panel from the unit. Locate the<br />
economizer control module, where the following adjustments<br />
will be made.<br />
Extreme care must be exercised in turning all set<br />
point, maximum <strong>and</strong> minimum damper positioning<br />
adjustment screws to prevent twisting them off.<br />
MIN<strong>IM</strong>UM POSITION ADJUSTMENT<br />
• Check that the damper blades move smoothly without<br />
binding; carefully turn the Minimum Position Adjust<br />
screw (found on the damper control module) fully clockwise<br />
<strong>and</strong> then set the thermostat indoor fan switch to the<br />
ON position <strong>and</strong> then OFF or energize <strong>and</strong> de-energize<br />
terminals “R” to “G”.<br />
Unitary Products Group 27