Page 6 I.L.15.01.T.K.<br />

Figure 3 - Typical Power Panel <strong>for</strong> 200-1200A models<br />

4.3 Table 1 - SYSTEMS COORDINATION INFORMATION –<br />

WITHSTAND, CLOSING & INTERRUPTING RATINGS<br />

ATS<br />

Ampere<br />

Rating<br />

Ratings when used with upstream<br />

breaker (kA)<br />

240V 480V 600V<br />

Ratings when used with upsteam<br />

fuse (kA)<br />

Max Fuse Fuse<br />

600V<br />

Rating Type<br />

30 100 65 25 200 J,T 200<br />

70 100 65 25 200 J,T 200<br />

100 100 65 25 200 J,T 200<br />

150 100 65 25 400 J,T 200<br />

225 100 65 35 400 J,T 200<br />

300 100 65 35 400 J,T 200<br />

400 100 65 35 600 J,T 200<br />

600 65 50 25 800/1200 J,T 100/200<br />

800 65 50 25 1200/1600 L 100/200<br />

1000 65 50 25 1600 L 200<br />

1200 65 50 25 1600 L 200<br />

Effective June 2000