Page 6 I.L.15.01.T.K.<br />
Figure 3 - Typical Power Panel <strong>for</strong> 200-1200A models<br />
4.3 Table 1 - SYSTEMS COORDINATION INFORMATION –<br />
WITHSTAND, CLOSING & INTERRUPTING RATINGS<br />
ATS<br />
Ampere<br />
Rating<br />
Ratings when used with upstream<br />
breaker (kA)<br />
240V 480V 600V<br />
Ratings when used with upsteam<br />
fuse (kA)<br />
Max Fuse Fuse<br />
600V<br />
Rating Type<br />
30 100 65 25 200 J,T 200<br />
70 100 65 25 200 J,T 200<br />
100 100 65 25 200 J,T 200<br />
150 100 65 25 400 J,T 200<br />
225 100 65 35 400 J,T 200<br />
300 100 65 35 400 J,T 200<br />
400 100 65 35 600 J,T 200<br />
600 65 50 25 800/1200 J,T 100/200<br />
800 65 50 25 1200/1600 L 100/200<br />
1000 65 50 25 1600 L 200<br />
1200 65 50 25 1600 L 200<br />