Technical description<br />
Application:<br />
Heating installations<br />
Arrangements:<br />
Regulating<br />
Shut-off<br />
Maximum and minimum restriction<br />
Nominal temperature range:<br />
See each product<br />
Temperature:<br />
Max. ambient temperature: 50°C<br />
Min. ambient temperature: -25°C<br />
Stroke:<br />
0.22 mm/K<br />
Heat transfer from inlet water:<br />
Thermostatic head with integral sensor and thermostatic head<br />
with remote setting: 0.4K<br />
Thermostatic head with remote sensor: 0.3K<br />
Replacement thermostatic head M28x1,5: 0.8K<br />
<strong>TERMORETT</strong> <strong>TRV</strong> <strong>300</strong> 1-<strong>10</strong>-5<br />
Thermostatic heads 2002.11<br />
Time to close:<br />
Thermostatic head with integral sensor 24 min<br />
Thermostatic head with remote sensor:<br />
Horizontally fitted sensor 12 min<br />
Vertically fitted sensor 15 min<br />
Hysteresis:<br />
0.2K<br />
TOUR & ANDERSSON AB<br />
Certification of Registration<br />
Number 2125 and 2125 M<br />
Certified by SP<br />
QUALITY AND ENVIRONMENT SYSTEM<br />
Marking:<br />
Thermostats are marked with <strong>TA</strong> and, where applicable, with<br />
the CEN symbol.<br />
Colour:<br />
White<br />
Materials:<br />
Plastic parts of ABS, acetal and nylon. Sensor element<br />
contains ethyl acetate liquid.
Thermostatic head<br />
With locking ring<br />
With two locking screws<br />
Allen key 2 mm<br />
Protective model<br />
<strong>TA</strong> No Temperature range<br />
50 340-028 6-28°C<br />
<strong>TA</strong> Nr Temperature range<br />
50 341-028 6-28°C<br />
<strong>TA</strong> Nr Temperature range<br />
50 343-028 6-28°C<br />
<strong>TA</strong> No Temperature range<br />
50 370-026 8-26°C<br />
1-<strong>10</strong>-5 - 2
Thermostatic head with remote sensor<br />
With locking ring<br />
With two locking screws<br />
Allen key 2 mm<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 340-127 6-27°C 1,25 m<br />
50 340-227 6-27°C 2 m<br />
50 340-527 6-27°C 5 m<br />
50 340-827 6-27°C 8 m<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 341-227 6-27°C 2 m<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 343-227 6-27°C 2 m<br />
To install the capillary tube in electric installation tube. Note: Tube without bends; use minimum 25 mm diameter. Tube with<br />
bends; use minimum 32 mm diameter.<br />
1-<strong>10</strong>-5 - 3
Thermostatic head with remote setting<br />
Thermostatic head with remote setting and remote sensor<br />
To install the capillary tube in electric installation tube. Note: Tube without bends; use minimum 25 mm diameter. Tube with<br />
bends; use minimum 32 mm diameter.<br />
Pocket tube and heat transfer cradle - see Accessories.<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 380-227 8-27°C 2 m<br />
50 380-527 8-27°C 5 m<br />
50 380-827 8-27°C 8 m<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 382-227 8-27°C 2 m x 1,5 m<br />
Thermostatic head with remote sensor for pocket tube or heat transfer cradle<br />
<strong>TA</strong> No Temperature range Capillary tube length<br />
50 364-201 20-50°C 2 m<br />
50 364-202 40-70°C 2 m<br />
1-<strong>10</strong>-5 - 4
Replacement thermostatic head M28<br />
Handwheel<br />
<strong>TA</strong> No Temperature range<br />
50 3<strong>10</strong>-028 6-28°C<br />
<strong>TA</strong> No<br />
50 399-003<br />
1-<strong>10</strong>-5 - 5
Function<br />
<strong>TRV</strong> <strong>300</strong><br />
When the ambient temperature rises above the set value of the thermostat, the fluid in the sensor expands and starts to close the<br />
valve.<br />
When the ambient temperature falls below the thermostat‘s set value, the fluid in the sensor contracts and the return spring in the<br />
valve starts to open the valve. When set to the frost protection position (*), the valve opens at a temperature of about 6°C in order<br />
to prevent the heating system from freezing.<br />
NB:<br />
If the <strong>TRV</strong> <strong>300</strong> with integral sensor is fitted vertically to a valve, with the sensor upwards, it may be affected by the heat from the<br />
pipe below and therefore close too early.<br />
In such cases, a thermostatic unit with a remote sensor should be used, with the sensor placed immediately beneath the radiator<br />
if possible or, if not, in the centre of the room.<br />
The scale on the thermostat represents a temperature change of 4°C between each numeral. Each mark on the scale represents<br />
a 1°C change.<br />
Thermostatic head with remote sensor for pocket tube or heat transfer cradle<br />
When the water temperature rises above the thermostat’s set value, the thermostat start to close the valve.<br />
When the water temperature falls below the set value, the return spring in the valve start to open the valve.<br />
Maximum temperature restriction<br />
Set the index opposite to the maximum room temperature required. E.g. number 3 corresponding to 20°C room temperature.<br />
1. Put the restriction pin in a little way opposite to number 5 to mark the correct pin position. Close the thermostat a little by turning<br />
it clockwise.<br />
2. Fully insert the restriction pin.<br />
3. Open the thermostat by turning it anti-clockwise and check that the index stops at a position corresponding to desired room<br />
temperature.<br />
Nominal temperature range<br />
The specified temperatures apply at the nominal lift height in accordance with CEN. Under normal operating conditions, the set<br />
temperature will be maintained with a maximum deviation of ±1K.<br />
Setting scales<br />
The closing temperature is normally 2K higher than ambient temperature.<br />
Thermostatic head with integral sensor / remote sensor<br />
The various settings give approximately the following room temperatures:<br />
Thermostatic head, protective model<br />
The various settings give approximately the following room temperatures:<br />
Thermostatic head with remote setting / remote setting and remote sensor<br />
The various settings give approximately the following room temperatures:<br />
Thermostatic head with remote sensor for pocket tube or heat transfer cradle<br />
The settings produce approximately the water temperatures shown on the thermostatic head.<br />
1-<strong>10</strong>-5 - 6
Accessories<br />
Setting key<br />
For thermostatic head, protective model<br />
Locking ring<br />
For thermostatic head with integral/remote sensor<br />
Key regulator<br />
4 mm allen key<br />
Restriction pin<br />
For thermostatic head with intergral/remote sensor<br />
Pocket tube for remote sensor<br />
For thermostatic head 50 364-201/-202<br />
<strong>TA</strong> No<br />
50 370-001<br />
<strong>TA</strong> No<br />
50 350-006<br />
<strong>TA</strong> No<br />
50 399-006<br />
<strong>TA</strong> No<br />
50 340-001<br />
<strong>TA</strong> No<br />
50 364-200<br />
1-<strong>10</strong>-5 - 7
Heat transfer cradle for remote sensor<br />
For thermostatic head 50 364-201/202<br />
Adapter M28-M30<br />
<strong>TA</strong> No<br />
50 364-203<br />
<strong>TA</strong> No<br />
50 357-530<br />
Tour & Andersson retains the right to make changes to its products and specifications without prior notice.<br />
1-<strong>10</strong>-5 - 8