6.18.4 Circulating pump electrical connections<br />

The external interlocks of unit must close for the unit to operate. The normally open external water circulating<br />

pump contactor terminals must be wired in series with terminals on the unit control panel, to ensure that the<br />

chiller can only start after the pump is in operation.<br />

In ST units external enabling contacts must be jumpered (unless they are required for system functions).<br />

See electrical drawing.<br />

6.18.5 Electric connection of the thermostat (optional)<br />

Connect the thermostat (supplied as option) with the electric panel of the indoor unit to the corresponding<br />

numbered terminals of the terminal boxes, as indicated in the electric diagram on board of unit.<br />

The section of the connection cables must not be less than 1.5 mm2.<br />

The thermostat must be installed properly in the conditioned room at about 1,5 m from the floor, in a position to<br />

measure the room temperature. The thermostat must therefore not be positioned in proximity of windows or<br />

doors, direct solar radiation and sources which could disturb the measure of the temperature.<br />

6.19 MICROPROCESSOR CONTROLLER<br />

Turn on the pump before the unit starts and stop it after the unit has<br />

stopped (recommended time delay: 60 sec.).<br />

For detailed information on the operation of this system, refer to the specific controller manual supplied with<br />

the unit.<br />

<strong>Air</strong> Blue • 23