6.15 AMBIENT AIR TEMPERATURE<br />

– The units are designed and built to operate with ambient air temperatures within the limits shown on the<br />

operating limits diagrams. Contact Bluebox if the unit is required to operate at different ambient temperatures.<br />

– It should be noted that the performance of heat pump units decreases significantly at lower ambient temperatures<br />

(below 0 °C).<br />

– The units can be optionally equipped with an electric element for heating the evaporator. The heater cuts<br />

in, when the machine is switched off, if the water temperature in the evaporator falls below the freeze<br />

protection calibration temperature.<br />

6.16 OPERATION IN LOW AMBIENT AIR TEMPERATURE CONDITIONS (OPTION)<br />

As ambient air temperature decreases it is possible to maintain the necessary condensation pressure for correct<br />

operation of the cooling cycle within the machine operating range by adjusting the cooling air flow through<br />

the condenser.<br />

Condensation pressure control is only active when the machine is operating in cooling mode.<br />

Condensation control is disregarded during heat pump mode operation.<br />

Condensation pressure regulation is achieved by a modulating damper that varies the air volume over the<br />

condenser coil in accordance with the condensing pressure read by the pressure transducers.<br />

6.17 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR<br />

Units from the normal production range are not designed to operate<br />

with chilled water temperatures lower than those indicated in the<br />

operating limit diagrams, at the evaporator outlet. To operate outside<br />

this limit the unit may require structural modifications. If this is<br />

necessary contact Bluebox.<br />

With temperatures lower than those shown in the operating limit diagrams, the hydraulic circuit should be filled<br />

with a suitable water and antifreeze solution. In such cases the service thermostat and the freeze protection<br />

thermostat must be reset:<br />

These calibrations are normally factory set.<br />

The ethylene glycol percentage must be selected in relation to the required chilled water temperature.<br />

See table 2.<br />

In the case of ST versions with a glycol content greater than 30%<br />

pumps with special seals must be specified at the time of the order.<br />

TABLE 2 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES<br />

LIQUID OUTLET TEMPERATURE<br />

OR MINIMUM AMBIENT TEMERATURE (°C)<br />

+0° -5° -10° -15° -20° -25° -30° -35° -40°<br />

FREEZING POINT (°C) -5° -10° -15° -20° -25° -30° -35° -40° -45°<br />

ANTIFREEZE % BY WEIGHT<br />

ETHYLENE GLYCOL 6 22 30 36 41 46 50 53 56<br />

PROPYLENE GLYCOL 15 25 33 39 44 48 51 54 57<br />

METHANOL 8 14 20 26 30 34 38 41 45<br />

CALCIUM CHLORIDE 9 14 18 21 24 26 27 28 30<br />

TEMPER. –20 T -20°C —<br />

TEMPER. –40 T -40°C —<br />

TEMPER. –60 T -60°C<br />

TIFOXITE 40 50 60 63 69 73 —<br />

FREEZIUM 10 20 25 30 34 37 40 43 45<br />

PEKASOL 50 50 59 68 75 81 86 90 —<br />

<strong>Air</strong> Blue • 21