6.15 AMBIENT AIR TEMPERATURE<br />
– The units are designed and built to operate with ambient air temperatures within the limits shown on the<br />
operating limits diagrams. Contact Bluebox if the unit is required to operate at different ambient temperatures.<br />
– It should be noted that the performance of heat pump units decreases significantly at lower ambient temperatures<br />
(below 0 °C).<br />
– The units can be optionally equipped with an electric element for heating the evaporator. The heater cuts<br />
in, when the machine is switched off, if the water temperature in the evaporator falls below the freeze<br />
protection calibration temperature.<br />
6.16 OPERATION IN LOW AMBIENT AIR TEMPERATURE CONDITIONS (OPTION)<br />
As ambient air temperature decreases it is possible to maintain the necessary condensation pressure for correct<br />
operation of the cooling cycle within the machine operating range by adjusting the cooling air flow through<br />
the condenser.<br />
Condensation pressure control is only active when the machine is operating in cooling mode.<br />
Condensation control is disregarded during heat pump mode operation.<br />
Condensation pressure regulation is achieved by a modulating damper that varies the air volume over the<br />
condenser coil in accordance with the condensing pressure read by the pressure transducers.<br />
6.17 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR<br />
Units from the normal production range are not designed to operate<br />
with chilled water temperatures lower than those indicated in the<br />
operating limit diagrams, at the evaporator outlet. To operate outside<br />
this limit the unit may require structural modifications. If this is<br />
necessary contact Bluebox.<br />
With temperatures lower than those shown in the operating limit diagrams, the hydraulic circuit should be filled<br />
with a suitable water and antifreeze solution. In such cases the service thermostat and the freeze protection<br />
thermostat must be reset:<br />
These calibrations are normally factory set.<br />
The ethylene glycol percentage must be selected in relation to the required chilled water temperature.<br />
See table 2.<br />
In the case of ST versions with a glycol content greater than 30%<br />
pumps with special seals must be specified at the time of the order.<br />
TABLE 2 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES<br />
LIQUID OUTLET TEMPERATURE<br />
OR MINIMUM AMBIENT TEMERATURE (°C)<br />
+0° -5° -10° -15° -20° -25° -30° -35° -40°<br />
FREEZING POINT (°C) -5° -10° -15° -20° -25° -30° -35° -40° -45°<br />
ANTIFREEZE % BY WEIGHT<br />
ETHYLENE GLYCOL 6 22 30 36 41 46 50 53 56<br />
PROPYLENE GLYCOL 15 25 33 39 44 48 51 54 57<br />
METHANOL 8 14 20 26 30 34 38 41 45<br />
CALCIUM CHLORIDE 9 14 18 21 24 26 27 28 30<br />
TEMPER. –20 T -20°C —<br />
TEMPER. –40 T -40°C —<br />
TEMPER. –60 T -60°C<br />
TIFOXITE 40 50 60 63 69 73 —<br />
FREEZIUM 10 20 25 30 34 37 40 43 45<br />
PEKASOL 50 50 59 68 75 81 86 90 —<br />