7. START-UP<br />

7.1 PRELIMINARY CHECKS<br />

– Check that the electrical connections have been made correctly, and that all terminals are well tightened.<br />

– Check that the voltage on the RST terminals is 400 V ± 5% (or the unit’s rated value, in the event of units<br />

supplied to run on non-standard power supplies). If the mains voltage is subject to frequent fluctuations,<br />

consult our Engineering Department to discuss the necessary protection systems.<br />

– Check that the display shows the gas pressure in the refrigerant circuit.<br />

– Inspect the unit for refrigerant leaks using a leak detector if necessary.<br />

– Check that the crankcase heaters are correctly supplied with power.<br />

Significant leakage of R407C refrigerant in the gaseous state will<br />

alter the percentages of the remaining mixture with consequent<br />

fall-off of performance.<br />

The heaters must be connected at least 12 hours before starting<br />

the unit; the heaters are automatically connected when the main<br />

disconnect switch is set to the ON position.<br />

– Verify that heaters are working correctly: after the warm up period the crankcase must be warm to the touch<br />

and must have at least a temperature 10 - 15 °C higher than ambient temperature.<br />

– Check that all hydraulic connections are correctly installed and all indications on unit labels are observed.<br />

– Check that the hydraulic system has been vent to eliminate any air remaining; charge it gradually and open<br />

the vent devices on the upper part, provided at the care of the installer together with an expansion tank of<br />

a proper size.<br />

Warning: before starting up the unit check that all the closing panels<br />

are in position and secured with the relative screws.<br />

<strong>Air</strong> Blue • 24