We strongly recommend installing a pressure relief valve on the<br />

hydraulic circuit (standard supply on version ST). In the event of<br />

serious system breakdown or emergency (e.g. fire), the system will<br />

be depressurised via the relief valve thus forestalling possible pipe<br />

bursts. Always connect the relief valve outlet to a pipe of diameter<br />

no smaller than the valve opening, and route it to a location in which<br />

persons are protected from the jet of expelled water.<br />

Caution: When making hydraulic connections never use naked flames<br />

close to or inside the unit.<br />

6.5 WATER FLOW SWITCH INSTALLATION INSTRUCTIONS<br />

– Clean the pipeline system into which the flow switch is to be fitted and take away any magnetic particle,<br />

such as welding residues.<br />

– Connect the “T” shaped metallic manifold (on which the flow switch is mounted) into the evaporator male<br />

threaded water outlet labelled with:<br />

Make the electrical<br />

connections on the<br />

terminal board<br />

USER WATER<br />

To avoid leakage, seal the connection by using teflon. The flow switch should be installed on the heat exchanger<br />

that is closer to the electrical board.<br />

User exchanger<br />

(evaporator)<br />

Figure 5<br />

<strong>Air</strong> Blue • 14