THIS BUILDING CONTAINS DUAL<br />

POWER SOURCES. THE SECOND<br />

5"<br />

SOURCE IS A PHOTOVOLTAIC<br />

SYSTEM. DISCONNECTS FOR THE<br />

SYSTEM ARE LOCATED AT THE SOLAR<br />

EQUIPMENT ENCLOSURE IN FRONT<br />

OF OR ADJACENT THE PV ARRAY<br />

5"<br />

A<br />

B<br />

C<br />

6"<br />

WARNING<br />

PLACARD TO BE PLACED NEXT TO METER OR MAIN<br />

SERVICE DISCONNECT<br />

SCALE: NTS<br />

Photovoltaic System<br />

Point Of Utility Connection<br />

Located Inside This Panel<br />

LABEL LOCATED ON MDP PANEL<br />

SCALE: NTS<br />

6"<br />

MAIN PV SYSTEM UTILITY<br />

AC DISCONNECT<br />

WARNING<br />

ELECTRIC SHOCK HAZARD<br />

DO NOT TOUCH TERMINALS<br />

SYSTEM CONNECTED TO THE CUSTOMER<br />

SIDE OF THE MAIN CIRCUIT BREAKER.<br />

INTERACTIVE SOLAR PV SYSTEM RATINGS<br />

MAX. OPERATING CURRENT 60A / POLE<br />

OPERATING VOLTAGE 120/208 VAC<br />

LABELS FOR UTILITY PV AC DISCONNECT SWITCH<br />

SCALE: NTS<br />

2 1 2 "<br />

2 1 2 "<br />

3"<br />

2 1 2 "<br />

G<br />

INVERTER 1<br />

Maximum DC Voltage: 68 V<br />

Normal Operating Voltage: 48 V<br />

Maximum AC Input Current: 60 A<br />

Normal AC Output Current: 60 A<br />

Maximum DC Input Current: 82 A<br />

SOLAR COMBINER BOX 1<br />

Maximum Open Circuit Voltage: 126 V<br />

Normal Maximum Power Voltage: 78 V<br />

Maximum Short Circuit Current: 64 A<br />

Normal Operating Current: 41 A<br />

4" 4" 4"<br />

WARNING<br />

Electric Shock Hazard<br />

DO NOT TOUCH TERMINALS<br />

Terminals on both Line and Load sides<br />

may be energized in the Open Position.<br />

DC VOLTAGE IS ALWAYS PRESENT WHEN<br />

SOLAR MODULES ARE EXPOSED TO SUNLIGHT<br />

WARNING<br />

120-Volt Supplies<br />

Do not connect three phase or multiwire<br />

branch circuits<br />

LABEL GOES ON STANDBY LOAD PANEL<br />

SCALE: NTS<br />

INVERTER 2<br />

Maximum DC Voltage: 68 V<br />

Normal Operating Voltage: 48 V<br />

Maximum AC Input Current: 60 A<br />

Normal AC Output Current: 60 A<br />

Maximum DC Input Current: 82 A<br />

SOLAR COMBINER BOX 2<br />

Maximum Open Circuit Voltage: 126 V<br />

Normal Maximum Power Voltage: 78 V<br />

Maximum Short Circuit Current: 64 A<br />

Normal Operating Current: 41 A<br />

WARNING<br />

Electric Shock Hazard<br />

DO NOT TOUCH TERMINALS<br />

Terminals on both Line and Load sides<br />

may be energized in the Open Position.<br />

DC VOLTAGE IS ALWAYS PRESENT WHEN<br />

SOLAR MODULES ARE EXPOSED TO SUNLIGHT<br />

H<br />

D<br />

E<br />

F<br />

INVERTER LABELS<br />

SCALE: NTS<br />

COMBINER BOX LABELS<br />

SCALE: NTS<br />

COMBINER BOX LABELS<br />

SCALE: NTS<br />

WARNING<br />

Electric Shock Hazard<br />

If a ground fault is indicated, normally<br />

grounded conductors may be<br />

ungrounded and energized.<br />

LABEL GOES ON FW1000DC-UNDER GFDI<br />

SCALE: NTS<br />

INVERTER 3<br />

Maximum DC Voltage: 68 V<br />

Normal Operating Voltage: 48 V<br />

Maximum AC Input Current: 60 A<br />

Normal AC Output Current: 60 A<br />

Maximum DC Input Current: 82 A<br />

SOLAR COMBINER BOX 3<br />

Maximum Open Circuit Voltage: 126 V<br />

Normal Maximum Power Voltage: 78 V<br />

Maximum Short Circuit Current: 51 A<br />

Normal Operating Current: 32.88 A<br />

WARNING<br />

Electric Shock Hazard<br />

DO NOT TOUCH TERMINALS<br />

Terminals on both Line and Load sides<br />

may be energized in the Open Position.<br />

DC VOLTAGE IS ALWAYS PRESENT WHEN<br />

SOLAR MODULES ARE EXPOSED TO SUNLIGHT<br />

I<br />

WARNING<br />

INVERTER OUTPUT CONNECTION<br />

DO NOT Relocate This<br />

Overcurrent Device.<br />

LABEL GOES NEXT TO PV BREAKER IN MAIN PANEL<br />

SCALE: NTS<br />

1369 14th Street, Baker, FL 32531<br />

Design for:<br />

I CERTIFY THAT THIS PV<br />

SYSTEM FULLY COMPLIES<br />

WITH THE REQUIREMENTS<br />

OF NEC 690.<br />

PV SYSTEM<br />

Total Output:<br />

# Modules:<br />

Manufacturer:<br />

Model:<br />

Baker School<br />

<strong>Solar</strong> School Shelters<br />

Battery Backup PV System<br />

Labels and Markings<br />

SCALE: NTS<br />

DRAWN BY: RB,HB<br />

CHECKED BY: EC<br />

DATE: 10/03/11<br />

SHEET 10 OF 20<br />

Revision:<br />

00<br />

10.08 kW<br />

42<br />

<strong>Solar</strong> World<br />

240<br />

Sheet:<br />

E.E. Castillo, PE<br />

Licensed Engineer #: PE52590<br />

Certification of Authorization #28406<br />

3601 N. DIXIE HWY, BAY 16 BOCA RATON, FL 33431<br />

PHONE: 561.750.8677 FAX:561.750.0518<br />

E-06