250A-160VDC in-line DC Fuse.<br />
Fuse - West Marine Model# 215089<br />
Fuse Block - West Marine Model# 10093813<br />
FlexWare Mounting Plate<br />
2 rows of 8 Batteries in series.<br />
Batteries are Sun Xtender 3050T Batteries.<br />
(See Sheet DS-03:04 for Battery Specifications).<br />
12.75"<br />
10.25"<br />
250A Inline DC Fuse<br />
Ground Anchor<br />
and Strap<br />
To positive DC Busbar in<br />
FlexMax 1000 Power<br />
Distribution Panel<br />
#2/0 To Negative DC<br />
Terminals Of<br />
Inverters<br />
# 4/0 From Battery<br />
Negative<br />
Conduit Tie Down bracket<br />
Wood Subfloor<br />
#4/0 battery cable<br />
Must be equal length 4/0 Battery Cables<br />
Battery Temperature Sensor Wire to one Charge Controller<br />
#4/0 battery cable<br />
Must be equal length<br />
4/0 Pos Battery<br />
Cable<br />
Battery Temp<br />
Sensor Wire<br />
Skids<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Concrete Block<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
#2/0 To Positive DC<br />
Terminals Of<br />
Inverters<br />
175 ADC<br />
# 4/0 From Battery<br />
Positive<br />
DC Busbar Detail in FlexMax 1000 Power Distribution Panel<br />
2" Flexible Metal<br />
Conduit<br />
Plastic Bushing<br />
4/0 Neg Battery<br />
Cable<br />
96.00"<br />
Battery Bank to DC Enclosure connection Detail<br />
Battery Wiring Detail<br />
SCALE: NTS<br />
2" Flexible Metal<br />
Conduit Connector<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Battery Temperature<br />
Sensor<br />
29"<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Battery Connection Detail<br />
Batteries are Concorde SunExtender PVX-3050T<br />
6V, 354Ah @ C/100 Battery bank supplies 27.0KWh @ 80% DOD<br />
Wiring Method:<br />
Battery System Wiring. Connect eight<br />
batteries in series to create a 48V array.<br />
Connect two groups in parallel. The<br />
batteries will deliver 27.0 kWh. Use only<br />
UL listed cables and lugs and UL listed<br />
crimp tools. Use 4/0 cables for battery to<br />
battery connections.<br />
Use only UL listed cables and lugs and UL<br />
listed crimp tool. Do not use fine stranded<br />
wire under the set screws inside the<br />
Outback Inverter.<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
Notes:<br />
Sun-Xtender<br />
PVX-3050T<br />
6V AGM Battery<br />
To negative DC Busbar in<br />
FlexMax 1000 Power<br />
Distribution Panel<br />
1. Batteries are Sun-Xtender PVX-3050T; 6<br />
volt batteries. Total battery capacity:<br />
27.0KWh @ (C/100) and 80% DOD.<br />
2. Positive and Negative battery cable<br />
length between batteries and busbar<br />
must be equal.<br />
3. Use heat shrink on all crimp lugs<br />
4. Disconnects for batteries are located on<br />
the FlexWare 1000 DC Power Distibution<br />
Panel.<br />
5. Install all batteries in accordance to NEC.<br />
6. Install Batteries in a well ventilated area<br />
to keep them as cool as possible.<br />
7. Fuse Information<br />
Fuse Rating: 250A@160VDC<br />
Manufacturer: Blue Sea Systems<br />
Manufacturer part #: 5118<br />
West Marine part #: 215089<br />
Fuse Block<br />
Model #: 10093813<br />
Manufacturer part #: 5502<br />
1369 14th Street, Baker, FL 32531<br />
Design for:<br />
I CERTIFY THAT THIS PV<br />
SYSTEM FULLY COMPLIES<br />
WITH THE REQUIREMENTS<br />
OF NEC 690.<br />
PV SYSTEM<br />
Total Output:<br />
# Modules:<br />
Manufacturer:<br />
Model:<br />
Baker School<br />
<strong>Solar</strong> School Shelters<br />
Battery Backup PV System<br />
Battery Wiring Detail<br />
SCALE: NTS<br />
DRAWN BY: RB,HB<br />
CHECKED BY: EC<br />
DATE: 10/03/11<br />
SHEET 8 OF 20<br />
Revision:<br />
00<br />
10.08 kW<br />
42<br />
<strong>Solar</strong> World<br />
240<br />
Sheet:<br />
E.E. Castillo, PE<br />
Licensed Engineer #: PE52590<br />
Certification of Authorization #28406<br />
3601 N. DIXIE HWY, BAY 16 BOCA RATON, FL 33431<br />
PHONE: 561.750.8677 FAX:561.750.0518<br />
E-04