A<br />

C<br />

Current Transducer Wiring<br />

SCALE: NTS<br />

<strong>Solar</strong> Irradiation Sensor Bracket<br />

SCALE: NTS<br />

Notes:<br />

Morning Star Relay Driver input voltage 8- 68VDC. Supply from<br />

battery or AC adapter.<br />

Relay Driver load without relays is 20mA.<br />

Individual Channel maximum output is 750mA<br />

Current transducer output voltage 0 - 10VDC.<br />

Current transducer sensor wiring #18 AWG<br />

Sensed wire must pass through center of current transducer window<br />

DC wiring colors: Black= NEG, Red= POS or per code.<br />

Notes: green House Computers, LLC<br />

This bracket is designed to mount a solar<br />

irradiance sensor in the plane of the array. Before<br />

affixing the irradiance sensor to the array, verify<br />

that the sensor is level with respect to the<br />

mounting bracket.<br />

Install such that shadows are not cast on an<br />

adjacent solar panel.<br />

green House Computers, LLC<br />

Title:<br />

Current transducer wiring, 120 /240 single phase<br />

Description:<br />

Wiring diagram showing two current transducers<br />

connected to a Morningstar Relay Driver.<br />

Title:<br />

<strong>Solar</strong> irradiation sensor Bracket<br />

Description:<br />

Bracket for mounting APRS6557 to solar array<br />

racking.<br />

B<br />

greenMonitor lite connector diagram<br />

SCALE: NTS<br />

green House Computers, LLC<br />

Austin, TX<br />

"Bringing Intelligence to <strong>Energy</strong> Conservation and Renewable <strong>Energy</strong>"<br />

SunSmart Schools System Content<br />

OutBack System Monitoring<br />

greenMonitor Lite, 8GB Flash, greenMonitor “Individual Advanced”<br />

software with Modbus enablement.<br />

15VDC / 120VAC adapter<br />

RS-232 Mate-wired serial cable, 6', shielded hoods.<br />

Cat 5 network cable, 7' (2m)<br />

4 port USB Hub, unpowered.<br />

Load Center Monitoring<br />

Critical Loads Panel (Inverter output connectors):<br />

Morningstar Relay Driver<br />

3 x Veris Industries Hawkeye 923 Current Transducer<br />

USB-to-Serial Adapter<br />

Grid Connection (Inverter input connectors):<br />

Morningstar Relay Driver<br />

3 x Veris Industries Hawkeye 923 Current Transducer<br />

USB-to-Serial Adapter<br />

Environmental Monitoring<br />

APRS World Wind Data Logger<br />

4x4 PVC junction box with 2 x 3/4” openings for power,<br />

communication and sensor wiring.<br />

15VDC / 120VAC adapter<br />

1' RS-232 to stripped leads pigtail, unshielded hood.<br />

USB-to-Serial Adapter<br />

#40R Anemometer<br />

1' anemometer stub, 1/2” galvanized EMT.<br />

Davis Instruments Pyranometer<br />

Pyranometer bracket<br />

Ambient temperature sensor, 30' cable<br />

Stevenson Screen for ambient temperature sensor<br />

Panel temperature sensor, 7' cable<br />

D<br />

Monitoring System Content<br />

SCALE: NTS<br />

Notes: green House Computers, LLC<br />

greenMonitor Lite includes<br />

Mate-wired serial cable, 7' (2m)<br />

Cat 5 /5E cable, Power over Ethernet (PoE)<br />

injector and 15 VDC 120 VAC adapter.<br />

Title:<br />

greenMonitor lite connector diagram<br />

Description:<br />

Diagram of connectors and indicator lights for a<br />

greenMonitor Lite.<br />

5 sensor combiner<br />

wind speed and direction (not included) with 3<br />

analog sensors to combined output<br />

5 sensor splitter<br />

combined input to wind and analog input<br />

50' patch cable<br />

splitter to combiner interconnection.<br />

2 x 1' Cat 5 patch cable<br />

splitter to wind and analog inputs<br />

splitter to wind and analog inputs<br />

1369 14th Street, Baker, FL 32531<br />

Design for:<br />

I CERTIFY THAT THIS PV<br />

SYSTEM FULLY COMPLIES<br />

WITH THE REQUIREMENTS<br />

OF NEC 690.<br />

PV SYSTEM<br />

Total Output:<br />

# Modules:<br />

Manufacturer:<br />

Model:<br />

Baker School<br />

<strong>Solar</strong> School Shelters<br />

Battery Backup PV System<br />

SCALE: green House NTS Computers, LLC<br />

DRAWN Drawn By: BY: Julie RB,HB Haugh<br />

CHECKED Date: 02 BY: /09/11<br />

EC<br />

DATE: 10/03/11<br />

SHEET 12 OF 20<br />

Revision:<br />

00<br />

10.08 kW<br />

42<br />

<strong>Solar</strong> World<br />

240<br />

Sheet:<br />

E.E. Castillo, PE<br />

Licensed Engineer #: PE52590<br />

green House Computers, LLC<br />

Monitoring System<br />

Certification of Authorization #28406<br />

3601 N. DIXIE HWY, BAY 16 BOCA RATON, FL 33431<br />

PHONE: 561.750.8677 FAX:561.750.0518<br />