Permit PackageBakerSchoolOkaloosa.pdf - Florida Solar Energy ...
Permit PackageBakerSchoolOkaloosa.pdf - Florida Solar Energy ...
Permit PackageBakerSchoolOkaloosa.pdf - Florida Solar Energy ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
A<br />
C<br />
3/4”<br />
Metal LB<br />
4”X4”X2”<br />
PVC<br />
Junction<br />
Box<br />
3/4” Sch 80 PVC<br />
W/ Cat 5<br />
12.75"<br />
40.5"<br />
Mate<br />
3/4” EMT<br />
Conduit<br />
Hub<br />
Input /Output<br />
Bypass Kit<br />
AC Breakers<br />
3/4” Sealing<br />
Locknut<br />
Exterior Wall Of School<br />
1” EMT<br />
Conduit<br />
1”<br />
Metal LB<br />
2 Hole PVC Strap<br />
11.5"<br />
OutBack FlexWare 1000 AC<br />
Power Distribution Panel<br />
(See Sheet E-03)<br />
6”X6”X4”<br />
PVC<br />
Junction<br />
Box<br />
Power in<br />
1” Sealing<br />
Locknut<br />
AC In<br />
H<br />
N<br />
AC Out<br />
H<br />
N<br />
AC In<br />
H<br />
N<br />
AC Out<br />
H<br />
N<br />
AC In<br />
H<br />
N<br />
AC Out<br />
H<br />
N<br />
To Shed To Shed To Shed<br />
1 1/4” EMT<br />
Conduit<br />
1 1/4”<br />
Metal LB<br />
GVFX3648<br />
PV BATT PV BATT<br />
-<br />
+<br />
-<br />
+<br />
GVFX3648<br />
GVFX3648<br />
FlexWare Mounting Plate<br />
47"<br />
Conduit Tie Down bracket<br />
2 rows of 8 Batteries in series.<br />
Batteries are Sun Xtender 3050T Batteries.<br />
(See Sheet DS-03:04 for Battery Specifications).<br />
4/0 Pos Battery<br />
Cable<br />
250A Inline DC Fuse<br />
Battery Temp<br />
Sensor Wire<br />
10.25"<br />
Wall<br />
Light Fixture<br />
GFCI Outlet<br />
Ground Anchor<br />
and Strap<br />
Outback GVFX Inverter<br />
AC Adapter<br />
DC Adapter<br />
Wood Subfloor<br />
-<br />
+<br />
Utility<br />
Disconnect<br />
15.25"<br />
Skids<br />
Power out<br />
9.25"<br />
Combiner Box A<br />
(See Sheet E-02)<br />
Concrete Block<br />
96.00"<br />
1 1/4” Hub<br />
Combiner Box B<br />
(See Sheet E-02)<br />
OutBack FlexWare 1000 DC<br />
Power Distribution Panel<br />
(See Sheet E-02)<br />
FW 1000<br />
DC Enclosure<br />
DC Breakers<br />
FLEXmax<br />
FLEXmax<br />
PV BATT<br />
Combiner Box C<br />
(See Sheet E-02)<br />
FLEXmax<br />
2" Flexible Metal<br />
Conduit<br />
Outback MX 80<br />
Charge Controller<br />
Cable Raceway<br />
Entrance<br />
PV+ and Batt+ Breakers<br />
Plastic Bushing<br />
4/0 Neg Battery<br />
Cable<br />
2" Flexible Metal<br />
Conduit Connector<br />
<strong>Solar</strong> Equipment Enclosure Interior South Elevation<br />
SCALE: 1/2"=1'0" B<br />
1" Sch 80<br />
Conduit w/10 # 12 USE-2<br />
& 1 #10 ground<br />
from Array<br />
to Combiner Boxes A, B, C<br />
Entrance<br />
29"<br />
8'<br />
In From PV Array<br />
Exterior Wall Of <strong>Solar</strong> Equipment Enclosure<br />
1" LB<br />
2 Hole PVC Strap<br />
3/4"<br />
LB<br />
3/4" Sch 80 Conduit<br />
w/mon wires From Array<br />
3/4" Sch 80 Conduit<br />
W/Cat5<br />
Meter 1<br />
Meter 2<br />
Out To Building<br />
36.00"<br />
1” Sch 80 PVC<br />
W/4 #6 &<br />
1 #10 Ground<br />
1 1/4” Sch 80 PVC<br />
W/ 4 #4 &<br />
1 #10 Ground<br />
1 1/4" Sch 80 1" Sch 80 Conduit<br />
Conduit<br />
w/4 #6, &<br />
w/4 #4 and 1 #10 Ground To<br />
Note: Use caulking<br />
around all wall<br />
penetrations.<br />
1 #10<br />
Ground To<br />
Building<br />
18” below grade<br />
Building<br />
18” below grade<br />
96.00"<br />
Combiner Box A<br />
(See Sheet E-02)<br />
1" Conduit from Array<br />
Single Door Entrance<br />
1" LB<br />
1" Conduit<br />
Combiner Box A<br />
(See Sheet E-02)<br />
<strong>Solar</strong> Equipment Enclosure Layout<br />
SCALE: 1/2" = 1'0"<br />
School Wall Connections<br />
<strong>Solar</strong> Equipment Enclosure North Elevation<br />
SCALE: 3/8"=1'0" D SCALE: 3/8"=1'0"<br />
E<br />
PV<br />
ARRAY<br />
Flexware<br />
Mounting<br />
Plate<br />
30.00"<br />
96.00"<br />
FlexWare 1000 DC Enclosure<br />
FlexWare 1000 AC Enclosure<br />
12.75"<br />
Combiner Box A<br />
(See Sheet E-02)<br />
PV<br />
ARRAY<br />
7"<br />
Meter 1 Meter 2<br />
Cat5 Wire Out<br />
Monitoring Wires From Array<br />
1'-4"<br />
4"<br />
Outback Combiner Box<br />
FlexWare 1000 AC Enclosure<br />
36.00"<br />
36.00"<br />
Minimum clearance needed<br />
Outback GVFX<br />
3648 Inverter<br />
Battery Bank<br />
2 Rows of<br />
8 Batteries in Series<br />
Wood Subfloor<br />
Skids<br />
Concrete Block<br />
72.00"<br />
Wall<br />
72.00"<br />
72.00"<br />
Vent (Mechanical-Optional)<br />
<strong>Solar</strong> Equipment Enclosure West Elevation<br />
SCALE: 3/8"=1'0"<br />
Light Fixture<br />
GFCI Outlet<br />
96.00"<br />
Ground Anchor<br />
and Strap<br />
N<br />
Notes:<br />
N<br />
This Drawing is<br />
intended to show<br />
equipment placement<br />
inside of enclosure<br />
only.<br />
See the attached<br />
enclosure plans for<br />
detailed enclosure<br />
specifications.<br />
1369 14th Street, Baker, FL 32531<br />
Design for:<br />
I CERTIFY THAT THIS PV<br />
SYSTEM FULLY COMPLIES<br />
WITH THE REQUIREMENTS<br />
OF NEC 690.<br />
PV SYSTEM<br />
Total Output:<br />
# Modules:<br />
Manufacturer:<br />
Model:<br />
Baker School<br />
<strong>Solar</strong> School Shelters<br />
Battery Backup PV System<br />
<strong>Solar</strong> Equipment Enclosure<br />
School Wall Detail<br />
SCALE: NTS<br />
DRAWN BY: RB,HB<br />
CHECKED BY: EC<br />
DATE: 10/03/11<br />
SHEET 15 OF 20<br />
Revision:<br />
00<br />
10.08 kW<br />
42<br />
<strong>Solar</strong> World<br />
240<br />
Sheet:<br />
E.E. Castillo, PE<br />
Licensed Engineer #: PE52590<br />
Certification of Authorization #28406<br />
3601 N. DIXIE HWY, BAY 16 BOCA RATON, FL 33431<br />
PHONE: 561.750.8677 FAX:561.750.0518<br />
M-02