Fire <strong>Protection</strong> <strong>Steel</strong> Spray CFP-S WB<br />

UL-listing BXUV.Y612 — Hollow <strong>Steel</strong> Sections<br />

* Hp/A = Heated Perimeter / Area<br />

** A/P = Area / Perimeter<br />

SP = <strong>Steel</strong> Pipe<br />

ST = <strong>Steel</strong> Tube<br />

<strong>Steel</strong> size Hp/A* A/P** 1 Hr 1-1/2 Hr 2 Hr 3 Hr<br />

Minimum dry Minimum dry Minimum dry Minimum dry<br />

thickness thickness thickness thickness<br />

mils mm mils mm mils mm mils mm<br />

SP 4.5 x 0.313 135 0.29 117 2.99 – – – – – –<br />

SP 8 x 0.875 49 0.79 97 2.46 97 2.46 120 3.05 – –<br />

SP 8.625 x 0.5 85 0.47 97 2.46 138 3.50 202 5.14 – –<br />

ST 3.5 x 3.5 x 3/16 224 0.18 165 4.18 – – – – – –<br />

ST 5 x 3 x 1/4 169 0.23 104 2.65 252 6.39 400 10.15 – –<br />

ST 5 x 3 x 5/16 135 0.29 84 2.13 218 5.54 353 8.96 – –<br />

ST 8 x 6 x 3/8 114 0.35 74 1.87 173 4.40 280 7.12 – –<br />

ST 8 x 6 x 7/16 100 0.41 74 1.87 151 3.84 244 6.21 – –<br />

ST 5 x 3 x 1/2 93 0.44 74 1.87 127 3.23 207 5.27 – –<br />

ST 8 x 8 x 1/2 85 0.47 74 1.87 95 2.41 164 4.17 327 8.31<br />

UL-listing BXUV.N631 — Beams<br />

<strong>Steel</strong><br />

size<br />

W/D 1 Hr 1-1/2 Hr 2 Hr 3 Hr<br />

Minimum dry Minimum dry Minimum dry Minimum dry<br />

thickness thickness thickness thickness<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

Unrestrained<br />

beam<br />

Restrained<br />

beam<br />

Unrestrained<br />

beam<br />

Restrained<br />

beam<br />

Unrestrained<br />

beam<br />

Restrained<br />

beam<br />

Unrestrained<br />

beam<br />

Restrained<br />

beam<br />

W6x12 0.52 73 1.83 73 1.83 99 2.50 73 1.83 171 4.34 101 2.56 – – – –<br />

W8x24 0.7 53 1.34 53 1.34 66 1.67 53 1.34 115 2.92 71 1.78 – – 158 4.00<br />

UL-listing BXUV.D975 — Concrete and <strong>Steel</strong> Floor Units<br />

Beams<br />

size<br />

W/D 1 Hr 1-1/2 Hr 2 Hr 3 Hr<br />

Minimum dry Minimum dry Minimum dry Minimum dry<br />

thickness thickness thickness thickness<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

mils<br />

mm<br />

Unrestrained<br />

beam<br />

Restrained<br />

Assembly<br />

Unrestrained<br />

beam<br />

Restrained<br />

Assembly<br />

Unrestrained<br />

beam<br />

Restrained<br />

Assembly<br />

Unrestrained<br />

beam<br />

Restrained<br />

Assembly<br />

W6x12 0.52 73 1.83 – – 123 3.10 – – – – 73 1.83 – – 123 3.10<br />

W8x24 0.7 53 1.34 – – 95 2.41 – – – – 53 1.34 – – 95 2.41<br />

<strong>Steel</strong> Floor Units W/D<br />

Fluted or Cellular 0.7 103 2.62 – – – – 103 2.62 – – – –<br />

Cellular 0.7 179 4.55 – – 341 8.67 179 4.55 – – 341 8.66<br />

6 <strong>Hilti</strong>, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I <strong>Hilti</strong> (Canada) Corp. 1-800-363-4458 I www.hilti.ca I CFP-S WB <strong>Submittal</strong> Information 8/2011