3. Analog Inputs<br />
2. Digital Inputs<br />
Motortronics<br />
Grp RTD# Fn# Function Adj. Range <strong>Inc</strong>r.<br />
F051 Input #1 (InP1) Select<br />
0-2 [0: Disabled; 1: Normally Open; 2:<br />
Normally Closed]<br />
Default<br />
Setting<br />
PSW<br />
Level<br />
1 0 1<br />
F052 Time Delay 1-60 (Sec) 1 1 1<br />
F053 Input #2 (InP2) Select<br />
0-2 [0: Disabled; 1: Normally Open; 2:<br />
Normally Closed]<br />
1 0 1<br />
F054 Time Delay 1-60 (Sec) 1 1 1<br />
F055 Input #3 (InP3) Select<br />
0-2 [0: Disabled; 1: Normally Open; 2:<br />
Normally Closed]<br />
1 0 1<br />
F056 Time Delay 1-60 (Sec) 1 1 1<br />
F057 Analog Input #1 Name<br />
0-5<br />
[0: OFF;<br />
1: Analog Input #1 (AnA1);<br />
2: Oscillation #1 (oSC1);<br />
1 OFF 1<br />
3: Air Flow #1 (AFL1);<br />
4: Speed #1 (SPd1);<br />
5: Pressure #1 (PrS1).]<br />
F058<br />
Analog Input #1 (AnA1)<br />
4mA<br />
0-9999 1 0 1<br />
F059<br />
Analog Input #1 (AnA1)<br />
20mA<br />
0-9999 1 9999 1<br />
F060<br />
Analog Input #1 Alarm<br />
Level<br />
0,1-9999 [0: OFF; 1-9999 trip level] 1 OFF 1<br />
F061<br />
Analog Input #1 Alarm Time<br />
1-60 (Sec)<br />
Delay<br />
1 1 1<br />
F062 Analog Input #1 Trip Level 0,1-9999 [0: OFF; 1-9999 trip level] 1 OFF 1<br />
F063<br />
Analog Input #1 Trip Time<br />
Delay<br />
1-60 (Sec) 1 1 1<br />
0-5<br />
[0: OFF;<br />
1: Analog Input #2 (AnA2);<br />
F064 Analog Input #2 Name 2: Oscillation #2 (oSC2);<br />
1 OFF 1<br />
3: Air Flow #2 (AFL2);<br />
4: Speed #2 (SPd2);<br />
5: Pressure #2 (PrS2).]<br />
F065<br />
Analog Input #2 (AnA2)<br />
4mA<br />
0-9999 1 0 1<br />
F066<br />
Analog Input #2 (AnA2)<br />
20mA<br />
0-9999 1 9999 1<br />
F067<br />
Analog Input #2 Alarm<br />
Level<br />
0,1-9999 [0: OFF; 1-9999 trip level] 1 OFF 1<br />
F068<br />
Analog Input #2 Alarm Time<br />
1-60 (Sec)<br />
Delay<br />
1 1 1<br />
F069 Analog Input #2 Trip Level 0,1-9999 [0: OFF; 1-9999 trip level] 1 OFF 1<br />
Note: See parameter Fn95 first to change between ºC and ºF.<br />