Motortronics<br />

2.2.4 Analog Output<br />

F071 – ANALOG OUTPUT SELECTION (0 – 6), Default Setting: 0 - OFF<br />

Select Output #1 Assignment:<br />

Setting Assignment<br />

0 OFF<br />

1 Hottest Stator RTD Temperature<br />

2 Hottest Non-Stator RTD Temperature<br />

3 Analog Input #1 (AnA1)<br />

4 Analog Input #2 (AnA2)<br />

5 Unit Internal Temperature<br />

6 Highest Differential Phase Current<br />

F072 – ANALOG OUTPUT 4mA (0 – 9999), Default Setting: 0<br />

Enter a value that the 4mA level will represent for the selected function; typically this value should be 0.<br />

F073 – ANALOG OUTPUT 20mA (0 – 9999), Default Setting: 9999<br />

Enter a value that the 20mA level will represent for the selected function.<br />

Example: Use Analog Output to measure Hottest Stator RTD temperature<br />

- Set F071 to 1 (Hottest Stator RTD)<br />

- Set F072 to 32 (32deg F = 4mA)<br />

- Set F073 to 464 (464deg F = 20mA)<br />

Analog Output Level<br />

20mA<br />

4mA<br />

F070<br />

F071<br />

Scaling<br />

www.motortronics.com Page 32