Motortronics<br />

2.2 Parameter Detailed Explanation<br />

2.2.1 RTD Settings<br />

F001 - STATOR PHASE A1 TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />

Select RTD #1 Type<br />

Setting Type<br />

0 OFF<br />

1 100 Ohm Pt (Platinum RTD)<br />

2 10 Ohm Cu (Copper RTD)<br />

3 100 Ohm Ni (Nickel RTD)<br />

4 120 Ohm Ni (Nickel RTD)<br />

F002 - RTD #1 DESCRIPTION SELECTION<br />

Select RTD Description Selection (0 – 1), Default Setting: 0 – Stator #1 (StA1)<br />

Setting Assignment<br />

0 Stator #1 (StA1)<br />

1 RTD #1 (rt 1)<br />

F003 - RTD #1 STATOR PHASE A1 ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr St 1” or<br />

“ALAr rt 1” is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />

on the setting of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

F004 - RTD #1 STATOR PHASE A1 TRIP <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature trip Level. When the RTD temperature reached this level trip “triP St 1” or “triP rt 1” is<br />

shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending on the setting<br />

of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />