Motortronics<br />
2.2 Parameter Detailed Explanation<br />
2.2.1 RTD Settings<br />
F001 - STATOR PHASE A1 TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />
Select RTD #1 Type<br />
Setting Type<br />
0 OFF<br />
1 100 Ohm Pt (Platinum RTD)<br />
2 10 Ohm Cu (Copper RTD)<br />
3 100 Ohm Ni (Nickel RTD)<br />
4 120 Ohm Ni (Nickel RTD)<br />
F002 - RTD #1 DESCRIPTION SELECTION<br />
Select RTD Description Selection (0 – 1), Default Setting: 0 – Stator #1 (StA1)<br />
Setting Assignment<br />
0 Stator #1 (StA1)<br />
1 RTD #1 (rt 1)<br />
F003 - RTD #1 STATOR PHASE A1 ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />
Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr St 1” or<br />
“ALAr rt 1” is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />
on the setting of F095.<br />
Range 0 – 240 Degrees Celsius (F095 = 0)<br />
Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />
F004 - RTD #1 STATOR PHASE A1 TRIP <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />
Set RTD Temperature trip Level. When the RTD temperature reached this level trip “triP St 1” or “triP rt 1” is<br />
shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending on the setting<br />
of F095.<br />
Range 0 – 240 Degrees Celsius (F095 = 0)<br />
Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />
www.motortronics.com Page 18