Motortronics<br />

F037 – RTD #10 TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />

Select RTD #10 Type<br />

Setting Type<br />

0 OFF<br />

1 100 Ohm Pt (Platinum RTD)<br />

2 10 Ohm Cu (Copper RTD)<br />

3 100 Ohm Ni (Nickel RTD)<br />

4 120 Ohm Ni (Nickel RTD)<br />

F038 - RTD #10 DESCRIPTION SELECTION<br />

Select RTD Description Selection (0 – 1), Default Setting: 0 – Ambient (Abnt)<br />

Setting Assignment<br />

0 Ambient (Abnt)<br />

1 RTD #10 (rt 10)<br />

F039 - RTD #10 ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr Abnt” or<br />

“ALAr rt10” is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />

on the setting of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

F040 - RTD #10 TRIP <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature trip Level. When the RTD temperature reached this level trip “triP Abnt” or “triP rt10” is<br />

shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending on the setting<br />

of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

F041 – RTD #11 TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />

Select RTD #11 Type<br />

Setting Type<br />

0 OFF<br />

1 100 Ohm Pt (Platinum RTD)<br />

2 10 Ohm Cu (Copper RTD)<br />

3 100 Ohm Ni (Nickel RTD)<br />

4 120 Ohm Ni (Nickel RTD)<br />

F042 - RTD #11 DESCRIPTION SELECTION<br />

Select RTD Description Selection (0 – 1), Default Setting: 0 – <strong>User</strong> Defined (USr1)<br />

Setting Assignment<br />

0 <strong>User</strong> Defined (USr1)<br />

1 RTD #11 (rt 11)<br />

www.motortronics.com Page 25